User`s guide
- 11 -
3.3 Communication Defaults
MODBUS slave ID or MODBUS address: 95 or 0x5F
MODBUS-RTU, 8 data bits, No Parity, 1 Stop bit (8-N-1),
19200 baud
3.4 Communication Settings Reset Jumper
MUST OPEN ENCLOSURE TO ACCESS
If the device’s communications settings are unknown, it is
possible to reset the communication settings by placing a
jumper on the RESET jumper position when the gateway is
not powered. This jumper is scanned at power up or reset.
Open jumper: Normal operation, Wireless and
MODBUS communications allowed to function.
Closed jumper: Communications interface reset.
If the jumper is detected closed, the device must be power-
cycled, with the jumper in the open position, before the
device is allowed to operate normally. During COM reset
the “Wired” indicator light will flash red indicating that the
reset procedure is happening.
3.5 Factory Reset Jumper
MUST OPEN ENCLOSURE TO ACCESS.
While in communication reset state, if the device remains
powered and the reset jumper is deliberately removed and
replaced twice, a factory reset will occur on the device.
All
indicators will flash red quickly (5x/sec) indicating that the
device has been successfully reset.
Power-cycle the device
with the jumper in the open position to allow normal
operation.
NOTE:
a factory reset will remove all known sensors and
settings from the device.