Universal Power Alert
ACSingle 40to600VAC,50/60/400Hz,
or3-Phase (LINE-TO-LINEorLINE-TO-GND)
DCorStored 30to1000VDC,
Energy (LINE-TO-LINEorLINE-TO-GND)
750VAC/1000VDC(LINE-TO-LINEor
LINE-TO-GND)
29VAC3-Phase,40VACSINGLE-Phase,
27VDC(TYPCutoff)
1.2Watts@750VAC(Approximately)
Operate -4°to131°F(-20°to+55°C)
Storage -40°to185°F(-40°to+85°C)
NEMA4X105°CPVC,TotallyEncapsulated
forEnvironmentProtection
(4)8ft,18AWG1000V,UL-1452
9oz.
3-PhaseLine-To-Line(VAC) <29 30 120 240 480 600 750
Flashes/Sec(Typical) 0 1.3 4.2 5.8 7.3 8.0 8.8
DCorStoredEnergy(VDC) <27 30 48 110 300 600 1000
Flashes/Sec(Typical) 0 1.6 2.5 4.5 6.9 8.8 9.1
3-PhaseLine-To-Line(VAC) 30 120 240 480 750
L1,L2,orL3ToGroundContinuity(OHMS
)2M 2M 3M 5M 7M
DetectorIncludedFaultCurrent(μA) 7 26 38 60 67
3-PhaseLine-To-Line(VAC) 30 120 240 480 750
0OHMPhase-To-GroundCurrent(μA) 28 108 219 455 730
UPA-100 UniversalPowerAlert
UPA-100S UniversalPowerAlert
Solid-ONRed
Accessories
UPA-WP100 WARNINGPlate
Thereducestheriskby
pre-verifyingtheelectricalisolationfromoutsideofacontrolpanel.Hard
wiredtothecircuitbreakerormaindisconnect,theUPAflasheswhenever
voltageispresent.Engineeredwith,thePowerAlert
ispoweredbythesamevoltagethatitindicates.
TheeightdetectorUPA-100visuallyalertstothepresenceofdangerous
ACorDC(StoredEnergy)potentialsoccurringbetweenanycombination
ofthefourmonitoredinputlines(L1,L2,L3,GND).TwoLEDindicators
areassignedtoeachinputlineandaredesignated“+”and“-”.For
eachinputlinecarryinganACpotential(bi-polar),boththe“+”and“-”
LEDswillbeactive.ADCorStoredEnergypotentialwillilluminatethe
“+”LEDforthepositivelineandthe“-”LEDforthenegativeline.
OSHA1910.147THECONTROLOFHAZARDOUSENERGY
(LOCKOUT/TAGOUT)
Following the application of lockout or tagout devices to energy isolating devices,
all potentially hazardous stored or residual energy shall be relieved, disconnected,
restrained, and otherwise rendered safe. (d)(5)(ii)
If there is a possibility of reaccumulation of stored energy to a hazardous level,
verication of isolation shall be continued until the servicing or maintenance is
completed, or until the possibility of such accumulation no longer exists. (d)(6)
“Verication of Isolation.” Prior to starting work on machines or equipment that
have been locked out or tagged out, the authorized employee shall verify that isola-
tion and de-energization of the machine or equipment have been accomplished.
ULTYPE
4X
• DetectsSingleor3-Phase
AC&DCVoltageor
StoredEnergy
• RedundantCircuitry
• VerificationofZeroEnergy
inaPanel
• Fits1-1/4"Conduit
Knock-Out
IND.CONT.EQ.
496Y
TheUPA-100SeriesisULListedunderULFileNumberE55826.