Specifications
Diversied Electronics 800.727.5646 atcdiversied.com
Diversied Electronics 800.727.5646 atcdiversied.com
Frequency NominalLine-to- Adjustable
LineVoltages Range
60Hz 208,220,240 200-250
380,415,440, 360-500
460,480,575,600 550-630
50Hz 208,220,240 200-250
346,380,415 330-430
Drop-out ±10%ofRangeSetting(Under/Over)
Pick-up ±7%ofRangeSetting(Under/Over)
120VAC±10%,50/60Hz
700VAC(Line-to-Line)
ABC(WillNotOperateOnCBASequence)
90VAMax.
2%to10%,AdjustableDrop-out
Hysteresis 10%ofSetting
13°Drop-out,12°Pick-up(Ø-Loss)
50/60Hz
Drop-out ±4%
Pickup ±3%
5CycleLockout,30-Min.CycleCountReset
AutomaticorManualMode
ClearsRapidCycleCount
DPDT,10A@240VACResistive
Flashing Continuous
Normal FaultDelay Relay
(GreenLED) Active Energized
Fault(RedLED) RestartDelay Relay
Active De-energized
Over(RedLED) RestartDelay Relay
Active De-energized
Unbal/ØLoss RestartDelay Relay
(RedLED) Active De-energized
PowerUp 2.5SMinimum
FaultDelay 0.1to25S,Adjustable
SevereFault 100mS(Ø-Loss,Unbalance
orØReversal)
Restart 0.5to300S,Adjustable(AutoReset)
Operate 32°to131°F(0°to+55°C)
Storage -49°to185°F(-45°to+85°C)
1%@FixedCondition
PlugandSocketTermBlockwithSpringPressureWire
Retention,12AWGMax.
35mmDINRailorSurfaceMount,PolycarbonateHousing
1.10lbs.
Universal Phase Monitor
SLU-600-ASTDS UniversalPhaseMonitor/Relay
IND.CONT.EQ
496Y
TheATC-DiversifiedElectronicsUniversalPhaseMonitorprotects
3-phasemotorsupto700VAC.Thefeaturepreventsmotorscyclingdue
toload-inducedlinefaultconditions.Poweredby120VAC,thisreliablemotorprotection
relayisunaffectedbytransientsanddisturbancesfromthemonitoredpowersource.The
SLU-600SeriesisULListedunderULFileNumberE55826.
• Monitorsupto700VAC
• DINRailorSurfaceMount
• OperatingRange
200-630VAC
• ManualorAutomaticReset
• AdjustableRestartDelay
• AdjustableFaultDelay
PROTECTSAGAINST:
• RapidCycling
• PhaseLoss
• PhaseReversal
• PhaseUnbalance
• PhaseShift
• Over/UnderVoltage
• Over/UnderFrequency










