Specifications
Diversied Electronics 800.727.5646 atcdiversied.com
Diversied Electronics 800.727.5646 atcdiversied.com
Integrated Duplex Controller
INCLUDES
INTRINSICALLY
SAFEINPUTS
Process
Control
Equipmentfor
Hazardous
Locations
7M26
UL913
24or120VAC±10%,50/60Hz
OpenCircuit 5VDC
Voltage
ShortCircuit 0.1mA
Voltage
4VAMaximum
Continuous
PowerUp 3SEC.±5%
InrushCurrent 5SEC.±5%
(3)SPST-N.O.10AmpResistive,1/4hp,278VA
Inductive@120VAC
Designation Color State Condition
Level/Alarm Red ON CS5Closed
Lag Green ON CS4Closed
Lead Green ON CS3Closed
Off Green ON CS2Closed
Aux.Off Green ON CS1Aux./cs2
Closed
Load1 Green ON LoadON
Load2 Green ON LoadON
Ctrl.Switch Red ON Failure
Open/Closed
Mechanical 20MillionOperations
Electrical 75,000@RatedLoad
Operate -4°to131°F(-20°to+55°C)
Storage -40°to185°F(-40°to+85°C)
(12)#8-32ScrewTerminals
16oz.
ARM-XXX-AFE* 24or120VAC Surface Standard
ARM-XXX-AFEP* 24or120VAC Panel Standard
ARM-2003 120VAC Surface Special:w/o
H-O-Aswitches
ARM-2010 120VAC Panel Special:w/o
H-O-Aswitches
ARM-2011 120VAC Surface Special:w/o
Controlswitch
failurefeature
*ReplaceXXXwithdesirecontrolvoltage(24,120)
TheAlternatingRelayisa
designedforuseindualloadinstallationstoassureequal
runtimeoneachload.LEDindicatorsshowthestatusoftheunit’s
fiveintrinsicallysafecontrolswitchinputs,onealarm,andtwoload
outputs.H-O-Aswitches,aleadselectswitch,andatest/clearbutton
areprovidedformanualcontrol.TheARMSeriesreducesthenumber
ofcomponentsrequiredforthisapplicationbycombiningmanyfunc-
tionsintooneunit.
Evenlydistributesruntimebyautomati-
callyalternatingleadandlagloaddesignationswhentheoffcontrol
switchinputopens.
Controlswitchinputsarelowvoltage/
lowcurrentandareelectronicallyisolatedfromthecontrolvoltage
andloadalarmcontacts.
H-O-ASwitches:Hand-Off-Automaticswitchesallowformanual
operation.
Disablestheautomaticsequencingfunction
andallowsloadstobelockedintothe2-1or1-2sequence.
Unitdetectsopenandshorted
controlswitchfailures.
Verifiesfunctionandresetsthecontrolswitch
faultdetectionalgorithm.
Alarmcontactsclosewhenacontrolswitchfailsor
thesystem’scapacityisexceeded.
Reduceslinesagsbypreventingboth
loadsfromenergizingsimultaneously.
Two(2)mountingconfigurationsareavail-
able.Thestandardsurfacemounthastopaccesstocontrolsand
indicatorsandisintendedforbackpanelmounting.Thepanelmount
optionisintendedforfrontpanelordoorcutoutaccesstocontrols
andindicators.
and–Standard
operationwithouttheH-O-Aswitches–Standard
operationwithouttheControlSwitchFailurefeature.
TheARMSeriesisULListedunderULFileNumberE151578.