Specifications

Diversied Electronics 800.727.5646 atcdiversied.com
Diversied Electronics 800.727.5646 atcdiversied.com
 
Triplexor
 24,120VAC±10%,50/60Hz

 2mA

  3VA(Approximately)

 Continuous
 Triplexor (3)5AmpResistive,1/6hp,211VA
@120VAC,InductiveExternally
Switchedtoterminal#2
Quadraplexor(4)5AmpResistive,1/6hp,211VA
@120VAC,InductiveExternally
Switchedtoterminal#2
 Mechanical 10,000,000Operations(Minimum)
Electrical 100,000Operations@RatedLoad
 LED’sShowConditionofOutputs
 Operate -4°to131°F(-20°to+55°C)
 Storage -40°to185°F(-40°to+85°C)
 Style“E”Lexan®SurfaceMounted
 (12)#8-32ScrewTerminals
 12to14oz.
NOTE:ForAnalogsignalinputs,ATCoffersaduplexingpumpcontrol
theATC-Digitec3800PanelMeter.
 ARA A E

24VTriplexor 24
120VTriplexor 120
120VQuadraplexor 120
Triplexor F
Quadraplexor(120Vonly) G
Thearedesigned
foruseininstallationsthatarerequiredtoalternate
insequencewhileassuringequalruntimeonallloads.Theyalsoallow
foradditionalloadstorunintheeventofexcessloadrequirements.
Thehavetheoptionofautomatic
alterationsorexternalclockingalterations.Whenthefactoryinstalled
jumperisinplacethealternatingactionisinitiatedbyacontrolswitch,
whichiscommonwithonesideofthecontrolvoltage.Whenthejumper
isremovedthealternatingactionisinitiatedbyanisolatednormally
openswitch.

Forautomaticalterationsafactory-installedjumperis
inplacebetweenterminals3and4.Thealternatingactionisaccom-
plishedwhenthecontrolswitchbetweenterminals2and4opens.
Forexternalclockingalterations,removethefactory-installedjumper
betweenterminals3and4andplaceanisolatednormallyopenswitch
betweenterminals2and3.Thealternatingactionwilloccureachtime
thisisolatedswitchisclosedandthenre-opened.

Forautomaticalterations,afactoryinstalledjumper
isinplacebetweenterminals11and12.Thealternatingactionisac-
complishedwhenthecontrolswitchbetweenterminals2and3opens.
Forexternalclockingalterations,removethefactory-installedjumper
betweenterminals11and12andplaceanisolatednormallyopen
switchbetweenterminals2and12.Thealternatingactionwilloccur
eachtimethisisolatedswitchisclosedandthenre-opened.
IntheeventofapowerfailuretheAlternatingRelayswillreturntotheir
quiescentstateandcontinuesequencingloadsonone-at-a-time.
IND.CONT.EQ.
496Y
TheARASeriesTriplexorandQuadraplexorareULListedunder
ULFileNumberE55826.