INSTALLATION
PPtl/PVC Condensate Tee-Joint
- joint fitting -
Fig. 28
Reference No Length I.D. O.D.
2255 10” 3.15” 4.92”
Length does not include drain spicket
Useful length after assy. 2”
PPtl/PVC Parallel Concentric Adapter (Male/Top)
- joint fitting -
Fig. 29
Reference No Length I.D. O.D.
2253 3.5” 3.15” 4.92”
PPtl/PVC Parallel Concentric Adapter (Female/Bottom)
- joint fitting -
Fig. 30
Reference No Length I.D. O.D.
2254 7” 3.15” 4.92”
45 degree Polypropylene Elbows
Fig. 31
Reference No Type Elbow Diameter
2258 45 degree 3.15”/80mm
2260 45 degree 4.33”/110mm
Typical Installation examples
Fig. 32
Options:
1 90 deg concentric
condensate T #2255
Rigid tube extentions # 2256
1 concentric vertical terminal #2206
1 sleeve tile roof flange
#9031& #9032
1 roof plate #2207
1 adjustable support #2208
1 parallel concentric adapter
# 2253 (male top)
1 parallel concentric
adapter # 2254
(female bottom)
Note: This is using the
Beckett NX Burner
Max L1= 32LF
Each 90* = 3.28lf
Each 45* = 1.64lf
Longer Venting Options:
Longer exhaust lengths can be achieved by using a Beckett
NX burner specifically modified and set up for use with the
FCX. When using the Beckett NX burner the maximum
unrestricted horizontal or vertical flue length shall be no more
then 36 feet if using an 80mm parallel piping system with
PPTL/PVC parallel concentric adapters on each end, or no
more then 30 feet if using concentric PPTL/PVC end to end.
The subtraction of 3.28 feet for 90 degree elbows and 1.6 feet
for 45 degree elbows still applies and must be taken into
account when figuring what the overall length is. It is
recommended that the Heatwise burner be used on overall
lengths of less then 16.4 feet and the Beckett be used on
lengths of 15 to a maximum of 36 feet.
The Beckett NX burner adapted for use on the FCX must have
the following specifications:
The oil line heater is standard with the burner.
The oil pressure is set to (150-155) PSI.
The oil nozzle used is a Danfoss .5-60 degree-AH.
NOTE: Do not use any larger size or supply nozzle with higher
pressure
Combustion readings should be CO 11 - 12.5, smoke 0 - .5