Service manual
7
www.monitorproducts.com
INSTALLATION
Fig. 17
Options:
Condensate Tee
Concentric extensions
1 concentric vertical terminal
1 sleeve tile roof flange
1 roof plate
Adjustable supports as needed
max L = L1 + 3.28 ft (1m) < 16.4 ft (5m)_
Fig. 18
Options:
Condensate Tee
3 Concentric extensions
2 45 deg concentric elbows
1 concentric vertical terminal
1 sleeve tile roof flange
1 roof plate
Adjustable supports as needed
_
Fig. 19
Options:
1 45 deg concentric elbow
Condensate Tee
Concentric extensions
1 concentric vertical terminal
1 sleeve tile roof flange
1 roof plate
max L = L1 + 1.64 ft (0.5 m) + 3.28 ft (1m) < 16.4 ft (5m)_
Note: Use fastening collars as needed. Support leg can consist of a fastening collar attached to a support such as a 2X6 joist.
Angled Balanced Flue Configuration
Fig. 16
Option: Angled Horizontal Flue Kit
max L = L1 + 1.64 ft (0.5m) + L2 + 1.64 ft (0.5m) + L3 +
3.28 ft (1m) < 16.4 ft (5m)
condensate tee
To provide
clearance
around water
connections a
45 degree
elbow can be
used.
To provide clearance
around water
connections a 1/2
meter concentric
extension can be
used
1 ft minimum
above max.
snow level
IMPORTANT: Total
lengths longer then 6 ft
(2 meters) should use a
concentric condensate
Tee, #2255, instead of the
concentric 90° elbow to
eliminate condensate
before draining back to
the unit. Condensate tee
must drain properly. It
can be tied into conden-
sate drain of the unit.
Use Condensate Tee
for lengths over 6ft