Specifications
v1.05
6.26.09
- 38 -
Monico
Id
PID Description Modbus
Address
Manual Remarks
24 Generator Phase Select 30026 0=Phase A-B Volts A current, 1=Phase B-C Volts B current,
2=Phase C-A Volts C current
27 Generator AC Voltage Full Scale and External PT
Setpoint
30029 0=700v, 1=150v, 2=300, 3=500, 4=600, 5=750, 6=3k,
7=4.5k, 8=5.25k, 9=9k, 10=15k, 11=18k, 12=30k
28 Generator AC Current Full Scale Setpoint (Read) 30030 starting at 0:
75,100,150,200,300,400,600,800,1k,1.2k,1.5k,2k,2.5k,3k,4k
Amps
33 ECM in Control (Marine Only) 30035 0=Primary ECM is controlling, 1=Backup ECM is controlling
61 Generator AC Voltage Full Scale Transformer Setpoint 30063 0=700v, 1=150v, 2=300, 3=500, 4=600, 5=750, 6=3k,
7=4.5k, 8=5.25k, 9=9k, 10=15k, 11=18k, 12=30k
62 Generator AC Current Full Scale Setpoint 30064 starting at 0:
75,100,150,200,300,400,600,800,1k,1.2k,1.5k,2k,2.5k,3k,4k
Amps
72 Remote Generator Synchronizer Control (GSP+P only) 30074 (This can be written to) 0=Off, 1=Remote synchronization
test, 2=Automatic synchronization
73 Remote Synchronization Control Readiness (GSP+P
only)
30076 0=Not installed, 1=ready for remote command,
2=Synchronizing switch not in auto, 3=Engine control switch
not in auto, 4 Engine was not started remotely, 5 Engine not
running
74 Generator Synchronizer Control Status (GSP+P only) 30077 Starting at 0: Not installed, Inactive, Semiautomatic
paralleling, Permissive paralleling, Remote synchronization
testing, Synchronizing, Synchronization system alarm or
diag., Remote synchronization testing passed, Dead bus time
delay, Closing to dead bus.
330
N
ormal Stop Input Status 30363 113=Run, 174=Stop
Multiple Status Bits
Read from Modbus register as unsigned integer. The value is composed of more than one status condition.
This is accomplished by setting the appropriate bits for each status condition. See details below:
Monico
Id
PID Description Modbus
Address
Manual Remarks
6 Oxygen Sensor Status 30006 Bits set to 1 indicate Status: 8=start cal. 7= cal in progress,
6=sensor on, 5= command sensor on
8 Ignition Timing Calibration 30008 Bits set to 1 indicate Status: 8=cal good else cal bad, 7=
enable cal else disable cal
42 G3600 Engine Status 30044 Bit8: 0=idle, 1=rated. Bit7: 0=off grid, 1=on grid. Bit6-5:
00=running, 01=coasting, 10=shutdown, 11=not used
43 Engine Operation 30045 Bit8: 0=genset, 1=industrial. Bit6: 0=isochronous governor,
1=droop governor
48 Auxiliary Status 30050 Mode Control Switch Bit8-7: 11=start, 10=auto, 01=stop,
00=off/reset. E-Stop Bit 6: 1=stop, 0=run. Driven
Equipment Bit5: 1=Ready, 0=Not Ready. Prelube Slave
Relay Bit 4: 1=ON, 2=OFF. Prelube Relay Bit3: 1=ON,
2=OFF. Prelube Switch Bit2: 1=Not Ready, 0=Ready.
Initiate Contact Bit1: 1=Stop, 0=Run.
55 EIS Special Test Status 30057 Inactive (Tests should only be done on-site) bit 8: 1=Enable
special test, 0=disable. Bit7: 0=proceed to test B. Bit5-1
0=test passed. Non zero=# of tests failed