Specifications
v1.05
6.26.09
- 30 -
59 Generator Phase A Power Factor Lead/Lag Status 30059 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
60 Generator Phase B Power Factor Lead/Lag Status 30060 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
61 Generator Phase C Power Factor Lead/Lag Status 30061 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
62 Generator Average Power Factor Lead/Lag Status 30062 0=Current lags voltage, 1=Current leads voltage, 224-255
Fault Identifiers*
67 EPG Circuit Breaker Status (GSP+P only) 30067 0=Breaker open, 1=Breaker closed, 228=Breaker sensor input
shorted low
151 Engine Coolant Pump Pressure Status 30151 0=coolant pressure OK, 1=coolant pressure too high, 2=Too
Low. 0-223 is Valid Range, 224-255 are Fault Identifiers
200 Hydrax Oil Pressure Switch Status 30200 22=Open, 23=Closed. 65504-65535 are Fault Identifiers
202 Emissions Feedback Mode 30202 394=Combustion Time Feedback, 395=Exhaust Temperature
Feedback, 397=Calibration Feedback, 398=No Feedback,
65504-65535 are Fault Identifiers
Multistate
Read from modbus register as unsigned integer. The value indicates different status conditions depending on
the value being read. See details below:
Monico
Id
PID Description Modbus
Address
Manual Remarks
22 Generator Phase Select 30022 0=Phase A-B Volts A current, 1=Phase B-C Volts B current,
2=Phase C-A Volts C current
25 Generator AC Voltage Full Scale and External PT
Setpoint
30025 0=700v, 1=150v, 2=300, 3=500, 4=600, 5=750, 6=3k,
7=4.5k, 8=5.25k, 9=9k, 10=15k, 11=18k, 12=30k
26 Generator AC Current Full Scale Setpoint (Read) 30026 starting at 0:
75,100,150,200,300,400,600,800,1k,1.2k,1.5k,2k,2.5k,3k,4k
Amps
31 ECM in Control (Marine Only) 30031 0=Primary ECM is controlling, 1=Backup ECM is controlling
57 Generator AC Voltage Full Scale Transformer Setpoint 30057 0=700v, 1=150v, 2=300, 3=500, 4=600, 5=750, 6=3k,
7=4.5k, 8=5.25k, 9=9k, 10=15k, 11=18k, 12=30k
58 Generator AC Current Full Scale Setpoint 30058 starting at 0:
75,100,150,200,300,400,600,800,1k,1.2k,1.5k,2k,2.5k,3k,4k
Amps
68 Remote Generator Synchronizer Control (GSP+P only) 30068 (This can be written to) 0=Off, 1=Remote synchronization
test, 2=Automatic synchronization
69 Remote Synchronization Control Readiness (GSP+P
only)
30069 0=Not installed, 1=ready for remote command,
2=Synchronizing switch not in auto, 3=Engine control switch
not in auto, 4 Engine was not started remotely, 5 Engine not
running
70 Generator Synchronizer Control Status (GSP+P only) 30070 Starting at 0: Not installed, Inactive, Semiautomatic
paralleling, Permissive paralleling, Remote synchronization
testing, Synchronizing, Synchronization system alarm or
diag., Remote synchronization testing passed, Dead bus time
delay, Closing to dead bus.
201
N
ormal Stop Input Status 30201 113=Run, 174=Stop