Firebox framing can be built before or after the appliance is
set in place. Construct rebox framing following Figure 4.1
for your specic installation requirements. Refer to Figure
4.1 on page 9 for rebox dimensions. The framing headers
may rest on the top of the rebox standoffs.
The rebox may be installed directly on a combustible oor
or raised on a platform of an appropriate height. When
the rebox is installed directly on carpeting, tile, or other
combustible material, other than wood ooring, the rebox
shall be installed on a metal or wood panel extending the
full width and depth of the enclosure.
WARNING!
Do not ll spaces around rebox with insulation
or other materials. This could cause a re.
WARNING!
The fireplace must be installed giving full
consideration to the clearance and height
requirements identied in this manual.
5. Mantel clearances: If a combustible mantel is installed,
it must meet the clearance requirements as shown in
Figures 6.3 & 6.4.
6. Floor clearance: This inner chamber rebox oor must
be installed at least 1" above any combustible ooring
material, such as carpeting or asphalt tile, which is
closer than 14" to the base of the rebox. See Figure 6.5.
Or
The inner chamber rebox oor may be installed nearer to
the oor if a minimum of 14" of noncombustible material
such as slate or marble is installed between the base of
the rebox and the combustible ooring. See Figure 6.6..
1” Min.
Combustible
Material
Figure 6.5 Floor Clearance Above Combustible Flooring Material
14”
Min.
Noncombustible
Material
Figure 6.6 Floor Clearance Above Noncombustible Flooring
Material
The classication "non-combustible material includes, but
is not limited to stone, brick, and mortar. Non-combus-
tibles are safe to overlay the black-painted metal face,
including radiant plates, and do not pose a re hazard.
Any non-combustible nish material must not extend past
or interfere with the replace opening.
The classication "combustible material," includes, but
is not limited to: plywood, drywall, and particle board.
Combustible materials may contact the sides, bottom,
or back of the rebox. Do not overlay the black-painted
face with combustible.
15