Owner's Manual

6
Clearances
Ensure that minimum clearances shown in Figures 6.1
through 6.4 are maintained. Left and right clearances are
determined when facing the front of the rebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
re hazard.
1. Sidewall clearances: The clearance from the inside
of the appliance to any combustible wall should not be
less than 6". See Figure 6.1.
2. Ceiling clearance: The ceiling must be at least 42"
from the top of the rebox opening. See Figure 6.1.
3. Back wall clearance: The appliance may be placed
against a combustible back wall.
4. Parallel wall clearances: The clearance from the
opening of the rebox to any wall that is parallel to the
opening should not be less than 36". See Figure 6.2.
NOTE: The canopy supplied with the unit must be installed
for correct mantel clearances.
Figure 6.3 Mantel Clearances
Figure 6.4 Mantel Leg Clearance
12”
10”
8”
6”
2½”
12”
14”
15½”
16¾”
18”
Combustible
Material Can
Contact Top
of Fireplace
Noncombustible Material
Only if Needed to Cover
Radiant Top Face
42"
Minimum
6"
Minimum
6"
Minimum
Figure 6.1 Clearance and Height Requirements
36”
(914 mm)
FP2320
wall clearance
Figure 6.2 Wall Clearance
Finish Wall
Combustible
Material Area
45°
B
A
6”
C
Fireplace
Hood
Top View
A B C
Combustible
in. 3 1 4
mm 76 25 102
Non-combustible
in. 0 6 6
mm 0 152 152
Grid represents 1/2" x 1/2"
14