Owner's Manual

9
71D0530
GCUF Vent-Free Fireboxes
FP2688
min floor combustible
5" Minimum
Combustible
Material
FP688
Figure 7 -
Minimum Clearance Above
Combustible Flooring

14” Minimum
FP2689
min floor clear noncomb
Can be Less
Than 5"
Noncombustible
Material
FP689
Figure 8 -
Minimum Clearance above Combustible Flooring with
Noncombustible Material Installed at Base of Fireplace

Firebox framing can be built before or after the appliance
is set in place. Construct rebox framing following Figure
1 for your specic installation requirements. See Figure 1
on Page 6 for rebox dimensions. The framing headers
may rest on the top of the rebox.
The rebox may be installed directly on a combustible oor
or raised on a platform of an appropriate height. When
the rebox is installed directly on carpeting, tile, or other
combustible material, other than wood ooring, the rebox
shall be installed on a metal or wood panel extending the
full width and depth of the enclosure.
The classication "noncombustible material" includes, but
is not limited to: stone, brick, and mortar. Noncombustibles
are safe to overlay the black-painted metal face, including
radiant plates, and do not pose a re hazard. Any noncom-
bustible nish material must not extend past or interfere
with the replace opening.
The classication "combustible material" incudes, but is
not limited to: plywood, drywall, and particle board. Com-
bustible materials may contact the sides, bottom, or back
of the rebox. Do not overlay the black painted face with
combustible materials.


     


      
   

 This inner chamber rebox oor must
be installed at least 5" above any combustible ooring
material, such as carpeting or asphalt tile, which is
closer than 14" to the base of the rebox. Figure 7
OR
The inner chamber rebox oor may be installed nearer to
the oor if a minimum of 14" of noncombustible ma terial
such as slate or marble is installed between the base of
the rebox and the combustible ooring. Figure 8