Operating instructions
42D0200
Designer Series Gas Fireplaces
9
The combustible area above the facing
must not protrude more than 3/4" from the
facing. If it does, it is considered a mantel and
must meet the mantel requirements listed in
this manual.
Figure 6 -
Mantel Clearances
2”
(51 mm)
4” (102 mm)
6” (152 mm)
8” (203 mm)
10” (254 mm)
4”
(102 mm)
6”
(152 mm)
8”
(203 mm)
10”
(254 mm)
12”
(305 mm)
FP2279
mantel clearance
2/09
Wall
Insulation Board
Standoff
Top of Louvers
FP2279
Any remote wiring (i.e. remote control, wall switch, and optional fan) must be done prior to
nal nishing to avoid costly reconstruction.
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL re rating
of Zero) may be used to cover the black-painted face of the appliance. A 300°F minimum adhesive
may be used to attach facing materials to the black surface. If joints between the nished wall and
the replace surround are sealed, a 300°F minimum sealant material (General Electric RTV103 or
equivalent) must be used. Combustibles may come to the top and side edges but not overlay the
face.