Operating instructions
14
42D0200
Designer Series Gas Fireplaces
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
It is important to select the proper length of vent pipe for the type of termination you choose. It is also
important to note the wall thickness.
Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 12"
of run towards the termination.
You may use up to three 90° elbows in this vent conguration. Refer to Horizontal Termination Congu-
rations on Pages 22 and 23.
Measure the distance from the replace oor to the ceiling. Add the ceiling thickness, the vertical rise in
an attic or second story, and allow for sufcient vent height above the roof line.
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when
using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination
of 90° and 45° elbows up to a maximum of 270°.
For two-story applications, restops are required at each oor level. If an offset is needed in the attic,
additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. Refer to
Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its balance between the combustion air intake and
the ue gas exhaust. Certain limitations apply to vent congurations and must be strictly followed.
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building.
A chase is required for such venting.










