Operating instructions
42D0200
Designer Series Gas Fireplaces
13
This appliance must be installed with an MHSC
approved venting system only.
Consult local building codes before beginning the
installation. The installer must make sure to select the
proper vent system for installation. Before installing vent
kit, the installer must read this replace manual and vent
kit instructions.
Only a qualied installer/service person should install vent-
ing system. The installer must follow these safety rules:
• Wear gloves and safety glasses for protection.
• Use extreme caution when using ladders or when
on rooftops.
• Be aware of electrical wiring locations in walls and
ceilings.
The following actions will void the warranty on your vent-
ing system:
• Installation of any damaged venting component.
• Unauthorized modication of the venting system.
• Installation of any component part not manufactured
or approved by MHSC.
• Installation other than permitted by these instruc-
tions.
**1"
*3"
FP2280
vent pipe clear
**1”
**1"
(25 mm)
**1”
*3" (76 mm)
326M”
(832 mm)
FP2280
until
the flue penetrates the outside wall.
Figure 13 -
Combustible Clearances for Vent Pipe
* A minimum of 3" clearance to the top is required along horizontal
length until ue pipe penetrates outside wall.
** A minimum 1" clearance to combustibles permitted all around
ue at outside wall.