Specifications
4/2
Schneider Electric
44
The Modicon Quantum Automation Series provides a highly flexible architecture that
ensures a cost-effective and high performance control solution, regardless of the
configuration. From centralized systems to highly distributed systems to networked
distributed control schemes, Quantum provides the right solution.
Quantum I/O can be used in three major architectures to meet control system
requirements:
b Local I/O.
b Remote I/O (RIO).
b Distributed I/O (DIO).
Whether your requirments are for improved space utilization, reduced installation
costs, high performance, or connectivity to HMIs and host computers, Quantum I/O
has an architecture that fits. Combining these different I/O architectures with
Quantum's wide range of communication options, an optimal control system can be
configured and installed to meet the most challenging control requirements.
Overview
Quantum Distributed I/O on Modbus Plus
Momentum I/O
DIO
DIO
Local I/O
Modbus Plus
Modbus Plus
Local I/O
Remote I/O
Remote I/O
Remote I/O
Quantum Remote I/O
I/O architecture selection Local I/O Remote I/O Distributed I/O
Media
– Coax Twisted pair
Maximum distance without repeaters
– 15,000 ft (4,572 m) 1,500 ft (457 m)
Speed
– 1.5 MHz 1MHz
Scan synched I/O servicing
– Yes No
Hot standby support
No Yes No
Momentum I/O support
– No Yes
Modbus Plus compatible
– No Yes
Maximum
– 31 63
Drops per network
I/O words per network
– 1,984 in/1,984 out 500 in/500 out
I/O words per drop
64 in/64 out 64 in/64 out 30 in/32 out
Discretes per network
– 31,744 in/31,744 out 7,840 in/7,840 out
Discretes per drop
1024 in/1024 out 1024 in/1024 out 480 in/512 out
Analogs per network
– 1,984 in/1,984 out 500 in/500 out
Analogs per drop
64 in/64 out 64 in/64 out 30 in/32 out
Networks per controller
– 1 3
Typical backplanes
6, 10, 16 slots 10, 16 slots 2, 3, 4 slots
Quantum automation platform 4
I/O architectures