Specifications

4/46
Schneider Electric
4
Characteristics (continued)
4
Quantum automation platform 4
Momentum analog I/O Bases
Characteristics of analog input bases (continued)
Type of base units 170 AAI 140 00 170 AAI 520 40
Number of inputs
1 x 16 single-ended input 1 x 4 differential inputs
Formatofdata
Full 16 bits signed (2's complement)
Protection Base and actuators
Polarity inversion
Error indication
None
Ranges
±10V ±5V 4…20 mA ±25mV ± 100 mV
Input impedance
k >2200 >2200 <0.250 > 10000 > 10000
Error at 25 °C
(% of full scale)
0.15 0.15 0.25 0.08 0.03
Error at 60 °C
(% of full scale)
0.25 0.25 0.45 0.18 0.09
Resolution
12 bits + sign 12 bits + sign 12 bits 15 bits + sign
Filtering
Low pass with cut-off frequency 10 kHz
Current source Pt100
mA 0.125
Ni100
mA 0.125
Pt1000
mA 0.125
Ni1000
mA 0.125
Update time
ms 1+1.5xn
n = number of declared channels
500
Error indication
None
Potential isolation Channel to channel
VDC None 400
Base power supply and Ground
VDC 500, 1 min 500, 1 min
Channels to ground
VAC 1780, 1 min 1780, 1 min
Base power
V ± 30 (voltage or current output) ± 30 (voltage or current output)
Common mode
Channel to ground
V ± 100 DC, 250 AC
Common mode
Voltage betw.channels
V 200 DC, 115 AC single phase or 3-phase
or 250 AC single phase
Common mode rejection Channel to ground
250 VAC at 47…63 Hz or 100 VDC 135dBDC,145dBAC50Hz,155dBAC
60 Hz
Between channels
120dBDC,130dBAC50Hz,140dBAC
60 Hz
Serial mode rejection
35 dB AC 50 Hz, 45 dB AC 60 Hz
Input protection
Polarity inversion
Operating voltage
VDC 24
Internal current
mA 305 @ 24 VDC
Power dissipation Typical
W 4.95 3.5
Maximum
W 5.55 5.5
Fusing Internal
2 A slow-blow 2 A slow-blow
External
500 mA fast-blow 500 mA fast-blow
Agency approvals
UL, e, CSA, FM Class I, Div. II
R
eferences :
p
ages 4/50 and 4/51
Dimensions :
page 4/51
Connections :
pages 4/52 and 4/53