Specifications
4/32
Schneider Electric
4
Characteristics (continued)
4
Quantum automation platform 4
Momentum discrete I/O Bases
Characteristics of discrete I/O bases (continued)
Type of base unit 170 ADM 350 10 170 ADM 350 11 170 ADM 350 15 170 ADM 370 10 170 ADM 390 10
Number of inputs
1x16 4x4 1x16
Number of outputs
2x8 2x4 1x8and1x4
Operating voltage
c V 24
Internal current
mA 250 @ c 24 V 250 @ c 24 V
(plus current for
sensors)
180 @ c 24 V
Inputs Voltage
c V 24
Type of signal
True high True low True high
Voltage at 1
c V +11…+30 - 3…+ 5 + 11…+ 30
Voltage at 0
c V -3…+5 +4…+30 - 3…+ 5
Input current
mA 2.5min.atstate1(6mA@c 24 V),1.2 max. at state 0
Input voltage range
c V -3…+30
Input resistance
kΩ 4
Response time
ms 2.2 Off to on
3.3Ontooff
0.06 Off to on
0.08 On to off
2.2 ms In, < 1 ms Out
3.3 ms In, < 1 ms Out
Fault sensing
– Broken wire
detection
Outputs Voltage
c V 24, 30 maximum
Type
Solid state switch
Type of signal
True high True low True high
Current capacity
A 0.5 per point
4 per group
8 per module
2 per point
8 per group
16 per module
0.5 per point
4 per group 1,
2group2
6 per module
Leakage current
mA <1@c 24 V <1@c 24 V <1@c 24 V
Peak current
A 5for1ms 2.8 for 1 ms –
On state voltage drop
c V <0.5@0.5A – –
Error indication
Output overload for at least one output to
communication adapter
Output overload
for at least one
output or short-
circuit or
overload on one
of the 4 encoder
supply groups,to
communication
adapter
Output
overload for at
least one output
to
communication
adapter
Response time
ms < 0.1 Off to On, < 0.1 On to Off
Potential isolation Input to input
None
Output to output group
None
Input to output group None
Field to communication interface V 500 AC
Power dissipation Typical
W 6.0 6.5
Maximum
W 8.0 10.0
Agency approvals
UL, e,CSA UL, e,CSA,FM
Class I, Div. II
R
eferences :
p
ages 4/35 and 4/36
Connections :
pages 4/37 to 4/41