User guide
TIO Power Supply Module
348
870 USE 101 00 V.2.2
Specifications,
Continued
Power on Surge
Current Curve
The following chart shows power on surge current for 120 VAC + 10% or 240 VAC +
10%.
DC Output
Voltage
This section contains specifications for DC output voltage:
Continued on next page
Number
1 x UB = 24 VDC, max. 0.7 A, isolated
Limiting Values
UBmin
21 VDC
UBmax
30 VDC
Output Current
IA
0 ... 0.7 A
Output Ripple
Typical
150 mV/p-p (max. 20 MHz)
Max.
250 mV/p-p (max. 20 MHz) - measured with a 0.1 microF capacitor
Voltage Regulation
Typically +500 mV for 0.7A after 0.35 A
Typically -500 mV for 0.35A after 0.7 A