User guide
TIO Power Supply Module
870 USE 101 00 V.2.2
345
Specifications
Overview
This section contains specifications for the 170 CPS 110 00 TIO Power Supply
module.
General
Specifications
The following table contains general specifications for the power supply module.
Continued on next page
Nominal Input Voltage
230 VAC or 120 VAC (jumper selectable)
Nominal Output Voltage
24 VDC
Maximum Output Current
(isolated)
0.7 A
Protective Circuitry
Inputs
Self-restoring fuse
Outputs
Overvoltage protection: limited by a transzorb diode (type:
SM6T30A)
Overload protection: by thermal current limiting (should the
thermal current limiting respond, the input voltage must be
switched -- off/on for reactivation).
Frequency
Input voltage
50/60 Hz + 5%
Internal chopper frequency
90 ... 110 kHz
Power
Efficiency
Typically 0.76 for IA = 0.7 A
Apparent power
Typically 32 VA for IA = 0.7 A
Effective power
Typically 21 W for IA = 0.7 A
Isolation
Input/output voltage‘
L, N, PE isolated from UB, M
Fusing
Input
Internal self-restoring fuse
Min external F1: for 230 VAC, 0.315 A, slow-blow
Min external F1: for 120 VAC, 0.63 A, slow-blow