User guide
Using Peer Cop with Concept
870 USE 101 00 V.2.2
309
Specifying References for Input and Output Data
Overview
We will now set up the 171 CCS 760 00 TSX Momentum M1 CPU at Modbus Plus
address 2 to:
send eight 4
x
registers of specific output to the supervisory computer at
Modbus Plus address 1.
receive five 4
x
registers of global input data from the ATRIUM supervisor.
These registers are the first five registers in a 10-register block of global
outputs broadcast by the supervisory controller.
Note:
For this example, we will use the default values for Health Timeout (500 ms)
and Last Value (Clear on timeout).
Defining the
Specific Output
The following table describes how to define the specific output, starting from the
Peer Cop dialog box.
Continued on next page
Step Action
1 Click on the Specific
Output...
button.
Result:
The Specific Output dialog box appears.