User guide

I/O Mapping an I/OBus Network with Concept
870 USE 101 00 V.2.2
285
Editing the I/OBus I/O Map
Overview
The maximum number of modules which can be I/O Mapped on the I/OBus network
depends on your Processor Adapter and its executive:
Note:
Concept 2.1 does not support the 171 CCC 760 10 Processor Adapter.
This Processor Adapter will be supported in Concept 2.2.
Procedure
To enter I/O bases or Interbus I/O modules using the Remote I/OBus Drop dialog,
perform the steps in the following table.
Continued on next page
Processor Adapter Executive Max. Modules Max. I/O Bits
171 CCS 760 00 984 128 2048
171 CCS 760 00 IEC 44 1408
Step Action
1 Click on the button
under the Module heading.
Result:
A list of module types is displayed, including I/OBus modules identified by
code number (a list of codes is provided at the end of this section):