User guide
Configuring an M1 CPU with Concept
274
870 USE 101 00 V.2.2
Stop Bit Should Not Be Changed
One Stop Bit
Each port operates with 1 stop bit. While Concept will allow you to select 2 stop
bits, this setting is invalid.
Changing Parity
Introduction
From the Modbus Port Setting screen, a port can be configured for even, odd, or no
parity checking. The factory-set default is EVEN parity.
Procedure
To change the parity parameter, perform the steps in the following table:
Step Action
1 Click on the down arrow under the
Parity heading.
Result:
A menu appears with the three Parity choices.
2 Click on the
None
,
Odd
or
Even
entry.
Result:
The Modbus Port Settings dialog box is updated with the Parity type you
have specified.