User guide

Using Peer Cop with Modsoft
216
870 USE 101 00 V.2.2
Devices on the Network
Introduction
This section describes the three CPUs which exchange data over the sample
Modbus Plus network and the strategy used to assign node addresses.
Devices
The three CPUs and their functions are described in the following table:
Address
Strategy
In this type of architecture, assign the lowest network address (1) to the
supervisory computer. When the network initializes, the supervisor will be the first
device to get the token, and the token rotation table will be built with respect to the
supervising device.
MB+ Address CPU Function
1 Pentium supervisory computer with
an AT984 host-based PLC card
Receives specific input data
and sends global outputs
2 171 CCS 760 00 TSX Momentum
M1 Processor Adapter with
172 PNN 210 22 Modbus Plus
Option Adapter
Controls I/OBus network
and exchanges data with
AT984 supervisor
3 171 CCS 760 00 TSX Momentum
M1 Processor Adapter with
172 PNN 210 22 Modbus Plus
Option Adapter
Controls I/OBus network
and exchanges data with
AT984 supervisor