Discrete I/O Bases
Characteristics of discrete input bases
Type of input base unit 170 ADI 340 00 170 ADI 350 00
170 ADI 540 50 170 ADI 740 50
Number of inputs 1x16 2x16
2x8
Input voltage
V
24 DC
120 AC 230 AC
Operating voltage
V
24 DC
85…132 AC
(@ 47…63 Hz)
164…253 AC
(@ 47…63 Hz)
Internal current
mA
250(@24VDC)
125 (@ 120 VAC) –
Input voltage range
V
- 3…30 DC
0…132 AC 163…253 AC
ON voltage
V
+ 11…30 DC
74 AC minimum 164 AC minimum
OFF voltage
V
- 3…+ 5 DC
20 AC maximum 40 AC maximum
Input current ON
mA
2.5 minimum
10.0 minimum 3…15
OFF
mA
1.2 maximum
2.0 maximum 0…15
Input resistance
kΩ
4
9.5 @ 50 Hz
7.5 @ 60 Hz
9@50Hz
7.5 @ 60 Hz
Type of signal True High
Response time On-off maximum
ms
3.3
35.0 @ 60 Hz 13.3 @ 60 Hz
Off-on maximum
ms
2.2
10.0 @ 60 Hz 13.3 @ 60 Hz
Potential isolation Grouptogroup
V
–
1780 AC
Field to communication
interface
V
500 AC
Power dissipation
W
3 typical,
5 maximum
5.5 typical,
8.5 maximum
–
Agency approvals UL, CE, CSA, FM
ClassI,Div.II
UL, CE, CSA UL, CE, CSA, FM
Class I, Div. II
UL, CE, CSA
Characteristics of discrete output bases
Type of output base unit 170 ADO
340 00
170 ADO
350 00
170 ADO
530 50
170 ADO
540 50
170 ADO
730 50
170 ADO
740 50
Number of outputs
2x8 2x16 2x4 2x8 2x4 2x8
Type of output
Solid state switch
Triac
Output voltage
V 24 DC 120 AC 230 AC
Operating voltage
V 24 DC 120 AC
(300 for 10 s, 400 for 1 cycle)
230 AC
(300 for 10 s, 400 for 1 cycle)
Internal current
mA 250 (@ 24 VDC) 125 65
Current Point maximum
A 0.5
2
0.5 2 0.5
Group
A 4
4
Module
A 8
8
Min. output current
mA – 5 30 5 30
Leakage current
mA <1@24VDC 1.9@120VAC 2.5 @
230 VAC
2.4 @
230 VAC
Surge current
A 5for1ms Point: 15 (1 cycle), 10 (2 cycles), 5 (3 cycles)
On StateVoltage drop
V <0.5DC@0.5A <1.5AC@
2A
<1.5AC@
0.5 A
<1.5AC@
2A
<1.5AC@
0.5 A
Protection (short-circuits, overloads)
Outputs electronically
protected
Via internal 5 A slow-blow fuse
Response time On-off maximum
ms <0.1 1/2 x 1/f (= 0,5 of one line cycle)
Off-on maximum
ms <0.1 1/2 x 1/f (= 0,5 of one line cycle)
Potential Isolation Output group
to output group
None None
Field to communication
interface
V 500 AC 1780 AC
Power dissipation
W 3.5 typical
4.5 maximum
6.0 typical
7.5 maximum
6.0 typical 7.5 maximum
Agency approvals UL, CE, CSA UL, CE, CSA UL, CE, CSA, FM Class I, Div. II
Characteristics
References :
pages 48237/7 to 48237/8
Connections :
pages 48237/9 to 48237/13
1780 AC