Models 499 NEH 104 10 499 NEH 141 00 499 NOH 105 10
Operating temperature
°C(F) 0to60(32to140)
Relative humidity
10…95% (non-condensing)
Dimensions W x H x D
mm
(in)
40 x 125 x 80
(1.58 x 4.92 x 3.15)
47 x 135 x 111
(1.85 x 5.31 x 4.37)
80 x 140 x 80
(3.15 x 5.51 x 3.15)
Weight
g(Lb) 520 (1.2) 240 (0.529) 900 (2)
Enclosure
IP 30
IP 20 IP 30
Agency approvals and compliance
cUL 1950; FM 3810; FM 3611 Class 1, Div. 2; CE, Germanischer Lloyd, IEC 61131-2
Characteristics
Models 499 NEH 004 10 499 NEH 041 00 499 NOH 005 10
Technology
Ethernet 10 Mbps Ethernet 100 Mbps Ethernet 10 Mbps
Interfaces
4 10baseT ports with
RJ45 shielded connectors
4 100baseTX ports with
RJ45 shielded connectors
- 3 10baseT ports with
RJ45
shielded connectors
- 2 10baseFL ports with BFOC
connectors
Connection type
Twisted pair cable Twisted pair cables or
redundant fibre optic ring
Terminal block
1 x 5-pin, pluggable
Operating voltage
VDC 18 to 32, safety low voltage
Redundancy
Power supply Power supply and optical ring
Power consumption at 24 VDC
mA 80 typical, 130 maximum 210 typical, 270 maximum 160 typical, 350 maximum
Maximum range
m(ft) Twisted pair line length, max 100 (max 330) Fiber optic, max 3100 (max
10,000)
Twisted pair, max 100 (max
330)
Number of cascaded hubs
4max 2max 4max
Number of hubs in a ring
11 max
Fault indicator
Power supply failure; permanent fault in hub; faulty link status of TP port; at least one port has
auto-partitioned
LED indicators
P1, P2 power, DA/STAT 1 to DA/STAT 4: data collision,
segmentation, and link status per port
P1,P2power,DA/STAT1to
DA/STAT 5: data collision,
segmentation, and link status
per port