User guide
0489Q-EN.fm/4
Schneider Electric
Selection guide (continued)
Momentum automation platform 0
Discrete I/O bases
Product type I/O modules for direct current
Type of signal True high True low True high
Input voltage 24 VDC
Operating voltage 24 VDC
Current consumption max. 250 mA max. 250 mA + sensor
current
Input type IEC 1131 Type 1+
Output voltage 24 VDC
Output type Solid state switch
Number of points 1 x 16 In, 2 x 8 Out 1x16In,2x4Out
Potential isolation
Point to point
group to group
Field to adapter
None
None
500 VAC
None
None
500 VAC
Current capacity
Per output
Per group
Per module
0.5 A
4A
8A
2A
8A
16 A
Response time
OFF-ON
ON-OFF
2.2 ms In, < 1 ms Out
3.3 ms In, < 1 ms Out
60 µsin,<1msOut
80 µsin,<1msOut
2.2 ms In, < 1 ms Out
3.3 ms In, < 1 ms Out
Protection against short
circuit and overload
Electrically safeguarded outputs Electrically safeguarded
outputs and 4 electronically
safeguarded sensor supply
group
Fault reporting
Output fault
I/O error
Blown fuse
1 LED/Out
to adapter
–
Type of module 170 ADM 350 10
170 ADM 350 11 170 ADM 350 15 170 ADM 370 10
Pages 48237/7