Specialty module I/O bases
Product type High-speed counter
Operating voltage 24 VDC
Unique features 2 independent, high-speed (10 kHz-200 kHz) counters
Modularity
Input channels
6 (3 per counter) True High Inputs
Output channels 4(2percounter)TrueHighOutputs
Input characteristics
Counter inputs
5 VDC differential input, 200 kHz counter; 24 VDC single-end input, 10 kHz counter
Discrete inputs 6 (2 x 3) 24 VDC inputs:
- voltage range, - 3 to + 30 VDC
- response time, 3 ms Off to On or On to Off
Output characteristics
Counter outputs
Two 5 VDC differential outputs min 20 mA @ 24 VDC
Discrete outputs 4 (2 per counter) 24 VDC outputs:
- on current, 0.5 A per point, 1 A per counter
- response time, < 0.1 ms Off to On; < 0.1 ms On to Off
Protection
Surge
Input voltage
45 V peak for 10 ms
Output current 5Afor1ms
Type of module
170 AEC 920 00