Specifications

16
FAULTFINDING
HELPFULHINTS
ShouldtheInverterappeartobemalfunctioningwesuggestthe
followingtoeliminateanyexternalproblems:
1. TurntheInverter“OFF”viatheCircuitBreakerswitchonthefrontpanel.
2. DisconnectallACwiringfromtheInverter.
3. DisconnectDCBatteryleadsfromBattery.Cleanallterminalsby
removingallgrease/corrosiononbothDCleadsandBattery
terminals.
4. EnsureyouhavesufficientBatterycapacityatthenominalvoltage
(specifiedonthecompliancelabelofyourInverter).
Pleasenote:Useminimum100AHBatteryorthesizeof
asubstantialCarBattery.
5. MakeconnectiondirectlytoBatteryterminalsandensureall
connectionsaretight.
7. EnsureBatteryvoltageiswithinthecorrectlimitsasoutlinedinthe
section ofthismanual.Ifyoudonot havea
DCvoltmeterormultimetercheckthefrontpanelforOvervoltsand
Undervolts EDs.
8. TurntheInverterONviatheCircuitBreakerswitchonthefrontpanel.
ObservethelightsonthefrontleftofyourInverter.Referto
forexplanationofIndicatorlights.
9. PluginvariousappliancesandmonitortheInvertersoperation.
* RememberthattheInverterautomaticallystartswhenaloadis
applied.
* Makesureleadsandterminalsarenotcorrodedorfaultyinanyway.
* MakesuretheInvertergoesintoSTANDBYwithnoloadswitchedon.
* MakesuretheCircuitBreakerisresetproperly.IfunsureswitchOFFand
ONagain.
6. RemoveotherwiringfrombatterytoensurethattheInverteristheONLY
deviceconnectedtobatterybank
sections
* Inextremeweatheritissuggestedtoshutdownandunplugtheunit.
INVERTERSPECIFICATIONS
INVERTER
OPERATION
L
DIPSWITCHSETTINGS
Dipswitchsettingsapplytoallmodelsfrom1000W-1800Winclusive.
InordertoaccesstheseoptionsyouhavetoopentheInverter.Before
alteringthesettingsswitchtheInverterOFF,adjustthesettingandswitchthe
InverterbackONagain.Werecommendtheseadjustmentsbecarriedoutby
qualifiedpersonneloryoursysteminstaller.
IfyouneedtooperateAmericanorJapaneseequipmentthisoptionwill
allowyourInvertertooperateat60Hz.
ThisfeatureisdesignedtorestarttheInverterandmaintainpowerintheevent
ofanexternalfault.ShouldtheInvertershutdownduetoundervoltage,over
temperatureoranyfaultconditionitwillattempttoresetevery8minutesuntil
thefaultconditionclearsandnormaloperationresumes.
ForoverloadshutdowntheInverterwillonlyattempt5restarts.IftheInverter
cannotresumenormaloperationwithin5restarts,itwillremainOFFuntilreset
manually.Thispreventscontinuousre-applicationofpowertofaulty
appliancesorwiring.
ForundervoltageshutdowntheInverterwillrestartwhenthebatteryvoltage
reachesthereconnectvalueasshowninthetablebelow.
SW5OFF&SW6OFF=(factorysetting)
SW1 Hz 50/60Hz
SW4 AR AutomaticReset
SW5&SW6 UV UnderVoltageSettings
Setting 12VValue 24VValue 48VValue
SW3 SP Special
SW5 SW6 DisconnectReconnect DisconnectReconnect DisconnectReconnect
ON ON 10.0 12.0 20.0 24.0 40.0 48.0
OFF OFF 10.5 12.5 21.0 25.0 42.0 50.0
ON OFF 11.0 13.0 22.026.0 44.0 52.0
OFF ON 11.5 13.5 23.027.0 46.0 54.0
ON=50Hz(factorysetting) OFF=60Hz
OFF=Disabled ON=Enabled (factorysetting)
SW2&
5