Installation and Service Manual
2-506.14
DIMENSIONAL/PERFORMANCE DATA
Table 6.1 - Outline Dimensions (inches)
Figure 6.1 - Outline Dimensions, VE Models 
(models VE50 thru 250 shown)
           Approx.
  Model  A  B  C  D  E  F  G  H  Fan Dia  Shipping Wt. - lbs.
 VE50  18  11 3/8  14 1/2  24 7/8  4 1/4  3 1/2  4 3/4  6 1/4  14  62
  VE75  18  11 3/8  14 1/2  24 7/8  4 1/4  3 1/2  4 3/4  6 1/4  14  64
  VE100  18  11 3/8  14 1/2  24 7/8  5  3 1/2  4 3/4  6 1/4  14  66
  VE150  18  11 3/8  14 1/2  24 7/8  5  3 1/2  4 3/4  6 1/4  14  70
  VE200  18  11 3/8  14 1/2  24 7/8  5  3 1/2  4 3/4  6 1/4  14  72
  VE250  18  11 3/8  14 1/2  24 7/8  5  3 1/2  4 3/4  6 1/4  14  73
  VE300  18  18 3/8  19 1/2  34 7/8  8 5/8  2 1/4  4 3/4  6 1/4  19  122
  VE400  18  18 3/8  19 1/2  34 7/8  8 5/8  2 1/4  4 3/4  6 1/4  19  125
  VE500  18  18 3/8  19 1/2  34 7/8  8 5/8  2 1/4  4 3/4  6 1/4  19  129
B
A
H
E
F
G
D
C
DIAMETER
7/8" DIAMETER  FOR
CONTROL WIRING .
MINIMU M  CLEARANCES:
AT LEAST  18"  FROM  CEILING
AND  24"  HORIZONTALLY  FROM
NEAREST  ENCLOSURE.
CEILING
SIDE  VIEW
TOP  VIEW
(4)  MTG  HOLES  1/2    13 N. C.  TAP 
MODELS  VE50  THROUG H  VE 25 0  SHOWN
B
FOR  POWE R  SUPPLY
(S EE  MINIMU M  CONDUIT
SIZE)
CEILING
SIDE VIEW
TOP VIEW
B
B 
D DIAMETER
FOR POWER SUPPLY 
(SEE MINIMUM CONDUIT 
SIZE)
MINIMUM CLEARANCES: AT 
LEAST 18" FROM CEILING 
AND 24" HORIZONTALLY 
FROM NEAREST 
ENCLOSURE
7/8" DIA. FOR 
CONTROL WIRING
(4) MTG. HOLES 1/2 - 13 N.C. TAP
Figure 6.2 - Outline Dimensions, PTE Models
12"
18-24"
24" 
MIN
CEILING 
WALL
5"
18"
MIN
6"
25-3/8"
34-7/8"
20-5/8"
8-5/8"
5-3/4"
7/8" OPENING FOR 
CONTROL WIRING
HANGER 
BRACKET 
(4) PROVIDED
4 MTG. HOLES
FRONT AND 
REAR 5/8" DIA.
1-3/8" OPENING
FOR POWER 
SUPPLY
Table 6.3 - Motor Specifications
Type Bearing
  Model  HP  Voltage  Phase Amperes Hertz  RPM
W/TOL Type
  VE50-100  1/15  208-230  1  1.28  60  1050  Totally Enclosed Shaded Pole  Sleeve
  VE150-250  1/8  208-230  1  1.00  60  1725  Totally Enclosed PSC  Ball
  VE/PTE300-500  1/6  208-230  1  1.54  60  1075  Totally Enclosed PSC  Ball
Table 6.2 - Performance Data (Models VE, PTE)
    Heating Capacity  Air Delivery Date (No Deflector) 
➀
        Outlet  Outlet Vel.  Temp.  Heat  Max. Mtg. 
 Model  KW  BTU/HR
        CFM  (FPM)  Rise °F  Spread (Ft)  Ht. (Ft)
  VE50  5.0 17,100  800 700 21  20  13
  VE75  7.5 25,600  800 700 31  17  11
  VE100  10  34,100  940 820 36  18  12
  VE150  15  51,200  1340 1170  38  26  17
 VE200  19  64,900  1600 1400  41  30  20
 VE250  25  85,400  1600 1400  55  26  17
  PTE/VE300 
 2-stage  30  102,000  2575 1240  40  31 ➁ 20 ➁
  PTE/VE400 
 2-stage  40  137,000  2575 1240  54  27 ➁ 18 ➁
  PTE/VE500 
 2-stage  50  171,000  2575 1240  70  24 ➁ 16 ➁
➀ With 70°F ambient air and heating at full capacity 
➁ See Figure 4.2 for PTE mounting height and heat 
throw
6