Brochure
2-116.7
3
ELECTRIC UNIT HEATERS
Horizontal air delivery unit heater type (HER series):
32 models, 8 sizes from 3 kW through 25 kW.
Recommended for buildings with low ceilings, they are equipped 
with horizontal air deflector blades to adjust airflow either up 
or down. Optional vertical deflector blades are also available 
to deflect air to the right or left, providing complete directional 
control over discharge of heated air. Horizontal delivery units 
are normally placed around the perimeter of the building where 
heat loss is greatest, so that the air stream from each heater 
“wipes” the wall to produce a blanket of warm air along the 
outside walls.
Vertical air delivery unit heater type (VE series):
21 models, 9 sizes from 5 kW through 50 kW.
Recommended for buildings with high ceilings are high and 
where obstructions do not permit good horizontal movement 
of air. Various optional air deflectors are available to produce 
a variety of distribution patterns (see page 12). Vertical unit 
heaters are usually oriented so that the heat spread from one 
overlaps the heat spread of another unit heater.
Power-Throw
TM
 unit heater type (PTE series):
3 models, 3 sizes from 15 kW through 50 kW.
For applications requiring heat throw greater than can be 
provided by HER units, Power-Throw
TM
 unit heaters should be 
considered. For hard-to-heat areas, such as near frequently 
opened loading dock doors or large warehouses, Power-Throw
TM 
units are frequently an ideal choice. They are equipped with 
horizontal air deflector blades to adjust airflow either up or 
down. Due to the higher velocity of discharge air, their air 
streams should not be directed at room occupants. A single 
Power-Throw
TM
 unit heater can often be used to replace as many 
as three smaller horizontal delivery units, thereby reducing 
equipment, installation, and maintenance costs.
Explosion Proof Horizontal Air Delivery Unit Heater Type 
(HEX series):
26 model combinations, 9 sizes from 3 kW through 35 kW.
These horizontal heaters are designed for rugged industrial 
applications in hazardous locations such as oil refineries, 
petrochemical plants, pulp and paper mills, coal mines, grain 
elevators, etc., where the possibility of explosion or fire exists 
due to the presence of flammable gases, vapors, powdered 
metals or dusts. Heaters are UL Listed for Class I, Divisions 1 
& 2, Groups C and D; Class II, Division 1, Groups E, F and G, 
and Class II, Division 2, Groups F and G. The UL temperature 
code shall be T3B 329°F (165°C) for Class I and II, indicating 
maximum operating surface temperatures. Before selecting 
any heater for a particular application, refer to Article 500 of the 
National Electric Code, as well as other applicable Standards. 
Abbreviated descriptions of UL classes, groups, and divisions 
are as follows.
Class I: Locations in which flammable gas or vapors may be 
present, such as, but not limited to:
• GroupC:Atmospheressuchasethylene,alcohol,carbon
monoxide, or hydrogen sulfide.
• GroupD:Atmospheressuchasacetone,gasoline,natural
gas, propane or other gases or vapors of equivalent hazard.
Class II: Locations in which combustible dusts may be present, 
such as, but not limited to:
• GroupE:Atmospherescontainingcombustiblemetaldust
regardless of resistivity or other combustible dust of similar 
hazard characteristics.
• GroupF:Atmospherescontainingcarbonblack,charcoal,
coal or coke dust or dust of similar hazard characteristics.
• GroupG:Atmospherescontainingflour,starch,graindust
or dusts of similar hazards.
Division I: Location in which ignitable concentrations of 
flammable material exist under normal operating conditions.
Division II:  Locations in which flammable materials will 
normally be confined within closed containers and escape only 
in the case of abnormal conditions. Any equipment approved for 
Division I is automatically also approved for Division II.
For further information, please consult the National Electric 
Code (NEC) and National Fire Prevention Association (NFPA) 
standards. 
Low Installation Cost
Transformers, contactors and fuses are factory-furnished 
and factory-wired when required. Terminal blocks facilitate 
connection of power supply and control wiring. Modine 
electric unit heaters are lightweight and require no special 
reinforcement to suspend them. 
Easy to Service
Fan and motor are exposed and can be removed without 
lowering the unit heater. A hinged bottom panel permits full 
access to controls on models HER, horizontal units. Vertical 
delivery and Power-Throw
TM
 models have separate control boxes 
externally mounted on the units. Motors are totally enclosed, 
permanently lubricated, and thermally protected. Electrical 
contactors, fuses, and transformers are all safely enclosed in 
control compartments.
Application Flexibility
Total Heating
Units can meet the total heating requirement in most industrial 
plants, commercial and recreational buildings, and in special-
purpose structures such as animal shelters. The features that 
make them the ideal selection for these types of buildings are a 
long heat throw, uniform heat delivery and low installation and 
maintenance costs. High up and out-of-the-way, unit heaters 
provide heat into work areas for clean, safe, economical heating 
comfort.
Supplemental Heating
They are ideal for spot heating applications during short 
periods of occupancy in the area to be heated. In out-of-the-
way locations, remote from areas served by the building’s main 
heating systems, electric unit heaters can often eliminate the 
expense of extending gas, steam, or hot water lines.
Stand-by/Back-up Heating
Where fossil fuel supplies are interruptible or undependable, 
electric unit heaters are recommended as a stand-by or back-up 
heating system to supply comfort to an entire building or any 
part of it. 
Wide Range of Sizes and Types
WARNING
Before installing and operating heaters confirm location, 
classification and properties of flammable vapors, liquids, 
gases, dusts and fibers which may be present. Each room, 
section or area should be considered individually.