A. Standards
A.1.a. Units shall be UL and C-UL listed for safe operation, 
construction, and performance. Units shall be listed for 
use in both the U.S. and Canada for commercial and 
industrial installations. (Models HER, VE, and PTE)
A.1.b. Explosion proof units, model HEX5 shall be UL listed and 
CSA certified for use in the following hazardous areas:
 •ClassI,Divisions1&2,GroupsC&D
 •ClassII,Division1,GroupsE,F&G
 •ClassII,Division2,GroupsF&G
 •ClassI,Zones1&2,GroupIIA&IIB
  Units shall be rated for National Electrical Code and 
Canadian Electrical Code Temperature Code T3B 165°C 
(329°F).
B. Mechanical Configuration
B.1.a. Heater shall be a Modine model HER horizontal air 
delivery electric unit heater of the size, capacity, and 
voltage as listed in the equipment schedule.
B.1.b. Heater shall be a Modine Power-Throw
TM
 model PTE 
horizontal air delivery electric unit heater of the size, 
capacity, and voltage as listed in the equipment schedule.
B.1.c. Heater shall be a Modine model VE vertical air delivery 
electric unit heater of the size, capacity, and voltage as 
listed in the equipment schedule.
B.1.d. Heater shall be a Modine model HEX5 horizontal air 
delivery electric unit heater of the size, capacity, and 
voltage as listed in the equipment schedule.
C. Unit Casing
C.1.  Unit shall have a steel casing that is treated for corrosion 
resistance and painted with an electrostatically applied, 
baked on, gray-green polyester powdercoat paint finish. 
(Models HER, VE, and PTE)
C.2.a. Model HER unit shall have a squared corner casing and 
the top shall have two threaded holes (3/8" - 16 TAP) for 
threaded rod suspension. The bottom of casing shall 
have a hinged panel for service access to wiring and 
controls.
C.2.b. Model PTE unit shall consist of two circular steel covers 
bolted together with the heating element supports. The 
air discharge side cover shall have a die-formed fan 
venturi. The back cover shall have a depression for 
motor mounting with openings for cooling-air circulation 
for the motor. Four hanging brackets shall be provided 
for use with 5/8” diameter suspension rods.
C.2.c. Model VE unit shall consist of two circular steel covers 
bolted together with the heating element supports. The 
bottom cover shall have a die-formed fan venturi. The 
top cover shall include an inner cone for motor mounting 
and to provide a heat shield from radiant and convective 
heat from the heating elements.
C.2.d. Model HEX5 shall be fabricated from 14 gauge steel 
with a baked epoxy powder coating over a 5-stage 
pretreatment including iron phosphate, for protection from 
corrosive atmospheres. The cabinet shall include two (2) 
9/16” mounting holes located on the top.
D. Heating Elements 
D.1.a. Elements shall consist of a nickel-chromium resistance 
wire surrounded with magnesium oxide and sheathed in 
steel spiral-finned tubes. Elements shall have kilowatt 
rating as listed in the equipment schedule. (Models HER, 
VE, and PTE)
D.1.b. The heat exchanger shall be fluid-to-air type consisting 
of steel tubes with roll-formed aluminum fins and 
be vacuum charged. The heat exchanger shall be 
protected by a preset 100 psig (690 kPa) pressure-relief 
valve, aluminum body, no serviceable parts. The heat 
exchanger shall be filled to design level with a custom-
blended, long-life solution of ethylene-glycol, water, and 
corrosion inhibitors. The heat exchanger shall have three 
heavy-duty immersion heating elements brazed into a 
heavy steel bulkhead. The elements shall consist of 
high-quality resistance wire embedded in a compacted 
magnesium oxide refractory and sheathed in metal 
tubing. The heater is to be protected by a snap-action 
bimetal temperature high-limit, which shall not be affected 
by altitude or changes in atmospheric pressure. The 
high-limit shall be an automatic reset type, and will shut 
off the heater if the exchanger temperature rises due to a 
lack of heat dissipation.
E. Motor and Propeller Fan 
E.1.a. Each unit shall have a single 208-230V/60Hz/1ph motor. 
The motor shall be totally enclosed, continuous-duty, 
with automatic resetting, thermal-overload protection. 
Propeller fan shall be directly connected to the motor 
shaft and be statically balanced. The motor shall be 
mounted to the unit with rubber vibration absorbing 
material. (Models HER, VE, and PTE)
E.1.b. Each unit shall have a ball bearing, permanently 
lubricated, thermally protected explosion-proof motor 
rated for continuous duty. The fan blades shall be 
aluminum to prevent sparking. Propeller fan shall be 
directly connected to the motor shaft and be statically 
balanced. The fan shall be shielded with a heavy-duty 
epoxy coated guard of two piece construction to provide 
easy maintenance and cleaning of the fan and motor. 
The guard shall not allow a 1/4" or larger probe to enter. 
(Model HEX5 only)
F. Electrical
F.1.  All units shall have built-in contactors and control circuit 
transformers (where required) to provide single-source 
power connection.
F.1.a. Models VE and PTE, sizes 300 through 500 shall have 
two sets of contactors to provide for two-stage operation.
F.1.b. Model HEX5 shall have a contactor coil that is 
encapsulated severe duty and separately fuse-protected.
F.2.  Fuse blocks and factory-supplied fuses shall be installed 
on all models except HER 30, 50, and 75 with 208 volt 
or 230-volt single or 3-phase power supply. A wiring 
diagram and grounding lug shall be included in each 
control compartment.
F.3.a. Transformers shall be factory installed on all models with 
460 volt, 3 phase power supply to permit 230 volt motor 
operation. (Models HER, VE, and PTE)
F.3.b. Transformers shall be factory installed on all HEX5 
models with the primary voltage being the same as the 
heater voltage and the secondary being 120V grounded 
circuit.
F.4.  Electrical control components shall be safely enclosed 
in a separate junction box. A wiring diagram and a 
grounding lug shall be included in each power junction box.
F.4.a. The Model HEX5 control center shall be enclosed in an 
explosion-proof control enclosure with a large threaded 
cover for easy access. The control center shall include 
a printed circuit board with a terminal block for room 
thermostat connection and in-line fuse protection, with 
both an operating fuse and a spare fuse.
F.5.  (opt) The HEX5 heater shall be supplied with a built-in 
explosion-proof room thermostat mounted on the control 
enclosure side of the heater.
G. Air Deflectors
G.1.a. Adjustable horizontal air deflectors shall be furnished. 
(Models HER and PTE)
G.1.b. Louvers shall be individually adjustable and made of 
anodized extruded aluminum. (Model HEX5)