Wiring Guide

Power HP BDP BDP BDP BDP BDP BDP BDP BDP BDP BDP BDP
Supply 50 75 100 125 150 175 200 250 300 350 400
115/1 1/4 6.0 6.0 6.0 6.0 6.0 - 6.0 - - - -
230/1 1/4 4.0 4.0 4.0 4.0 4.0 - 4.0 - - - -
200/3 1/4 2.6 2.6 2.6 2.6 2.6 - 2.6 - - - -
230/3 1/4 2.5 2.5 2.5 2.5 2.5 - 2.5 - - - -
460/3 1/4 1.9 1.9 1.9 1.9 1.9 - 1.9 - - - -
575/3 1/4 1.8 1.8 1.8 1.8 1.8 - 1.8 - - - -
115/1 1/3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 7.3 - - -
230/1 1/3 3.8 3.8 3.8 3.8 3.8 3.8 3.8 3.8 - - -
200/3 1/3 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 - - -
230/3 1/3 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 - - -
460/3 1/3 1.9 1.9 1.9 1.9 1.9 1.9 1.9 1.9 - - -
575/3 1/3 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 - - -
115/1 1/2 10.3 10.3 10.3 10.3 10.3 10.3 10.3 10.3 - - -
230/1 1/2 5.3 5.3 5.3 5.3 5.3 5.3 5.3 5.3 - - -
200/3 1/2 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 - - -
230/3 1/2 3.4 3.4 3.4 3.4 3.4 3.4 3.4 3.4 - - -
460/3 1/2 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 - - -
575/3 1/2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 - - -
115/1 3/4 13.3 13.3 13.3 13.3 13.3 13.3 13.3 13.3 - - -
230/1 3/4 6.7 6.7 6.7 6.7 6.7 6.7 6.7 6.7 - - -
200/3 3/4 4.1 4.1 4.1 4.1 4.1 4.1 4.1 4.1 - - -
230/3 3/4 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 - - -
460/3 3/4 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 - - -
575/3 3/4 2.3 2.3 2.3 2.3 2.3 2.3 2.3 2.3 - - -
115/1 1 - 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 -
230/1 1 - 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 -
200/3 1 - 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 4.9 -
230/3 1 - 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 4.8 -
460/3 1 - 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 -
575/3 1 - 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 -
115/1 1-1/2 - - - 17.5 - 17.5 17.5 17.5 17.5 17.5 17.5
230/1 1-1/2 - - - 8.9 - 8.9 8.9 8.9 8.9 8.9 8.9
200/3 1-1/2 - - - 6.1 - 6.1 6.1 6.1 6.1 6.1 6.1
230/3 1-1/2 - - - 6.1 - 6.1 6.1 6.1 6.1 6.1 6.1
460/3 1-1/2 - - - 3.6 - 3.6 3.6 3.6 3.6 3.6 3.6
575/3 1-1/2 - - - 3.1 - 3.1 3.1 3.1 3.1 3.1 3.1
115/1 2 - - - - - - - - - - -
230/1 2 - - - - - - - - - - -
200/3 2 - - - - - 8.1 - 8.1 8.1 8.1 8.1
230/3 2 - - - - - 7.3 - 7.3 7.3 7.3 7.3
460/3 2 - - - - - 4.3 - 4.3 4.3 4.3 4.3
575/3 2 - - - - - 3.5 - 3.5 3.5 3.5 3.5
115/1 3 - - - - - - - - - - -
230/1 3 - - - - - - - - - - -
200/3 3 - - - - - - - - 11.2 11.2 11.2
230/3 3 - - - - - - - - 9.5 9.5 9.5
460/3 3 - - - - - - - - 5.4 5.4 5.4
575/3 3 - - - - - - - - 4.6 4.6 4.6
115/1 5 - - - - - - - - - - -
230/1 5 - - - - - - - - - - -
200/3 5 - - - - - - - - - 16.5 16.5
230/3 5 - - - - - - - - - 14.3 14.3
460/3 5 - - - - - - - - - 7.8 7.8
575/3 5 - - - - - - - - - 6.5 6.5
i
Unit Power Requirements (AMPS) – PDP Models
Unit Power Requirements (AMPS) – BDP Models
Power PDP 30, PDP 75, PDP 125, PDP 175, PDP 250 PDP 300 PDP 350,
Supply 50 100 150 200 400
115/1 2.7 3.3 4.0 5.1 7.7 9.8 11.1
208/1 1.3 1.9 1.9 2.8 - - -
208/1
2.4 2.4 2.4 4.8 4.8 7.2 7.2
230/1 1.3 1.9 1.9 2.8 3.7 4.7 5.5
230/1 2.2 2.2 2.2 3.3 4.4 6.5 6.5
208/3 2.4 2.4 2.4 4.8 4.8 7.2 7.2
230/3 2.2 2.2 2.2 3.3 4.4 6.5 6.5
460/3 1.1 1.1 1.1 1.6 2.2 3.3 3.3
575/3 0.9 0.9 0.9 1.3 1.7 2.6 2.6
6-446 — MODELS PDP/BDP
With accessory transformer.