Use and Care Manual

Model Size
50 75 100 125 150 175 200 250 300 350 400
12 14 16 18 18 18 18 22 24 24 24
4 5 5 6 6 9 6 8 8 8 8
12 14 17 18 20 26 18 24 26 24 24
17 21 25 26 29 37 26 35 38 36 35
10 14 16 18 18 18 18 22 24 24 24
00000000000
14 10 13 12 13 23 12 16 19 16 16
19 14 19 17 19 32 17 23 28 24 23
12 16 20 20 22 22 22 28 30 30 30
12 16 19 21 23 25 22 29 32 20 29
14
Standard Model Number
PDP 30 PDP 50 PDP 75 PDP 100 PDP 125 PDP 150 PDP 175 PDP 200 PDP 250 PDP 300 PDP 350 PDP 400
Btu/Hr. Input 30,000 50,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr. Output 24,000 40,000 60,000 80,000 100,000 120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow (CFM) 440 740 1100 1460 1850 2180 2550 2870 3700 4460 4870 5440
Outlet Velocity 515 610 736 860 870 931 959 819 1053 1123 1068 1016
Air Temp. Rise (°F) 51 50 51 51 50 51 51 52 50 50 53 54
Max. Mounting Hgt.
(Ft) 7 9 12 14 14 16 17 15 19 21 20 19
Heat Throw (Ft)
(Max. Mtg. Hgt.) 25 33 41 49 51 55 59 51 67 74 70 69
Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC PSC PSC
115/60/1 (PC01) 1/40 1/40 1/12 1/12 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
230/60/1 (PC02) 1/40 1/40 1/8 1/8 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
200-208/60/1 (PC03)
1/40 1/40 1/8 1/8 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
GENERAL PERFORMANCE DATA
Table 14.1 - Performance — Propeller Models
➀ ➁
Table 14.2 - Motor Data and Total Unit Power Requirements — Propeller Models
Unit Voltage 115/60/1 115/60/1 With Use of Transformer 208/60/1 230/60/1
Supply Voltage 115/60/1 208V 230V 460V 575V 208/60/1 230/60/1
Mtr. Mtr. Total Max KVA Total KVA Total KVA Total KVA Total Mtr. Mtr. Total Max Mtr. Mtr. Total Max
Amps Rpm Amps Watts Req. Amps Req. Amps Req. Amps Req. Amps Amps Rpm Amps Watts Amps. RPM Amps Watts
1/40 1.0 1550 2.7 320 0.50 2.4 0.50 2.17 0.50 1.09 0.50 0.87 0.4 1550 1.3 270 0.4 1550 1.3 300
1/12 1.6 1625 3.3 400 0.50 2.4 0.50 2.17 0.50 1.09 0.50 0.87 --- --- --- --- --- --- --- ---
1/8 2.3 1625 4.0 480 0.50 2.4 0.50 2.17 0.50 1.09 0.50 0.87 1.0 1625 1.9 400 1.0 1625 1.9 440
1/6 2.7 1075 5.1 610 1.00 4.81 0.75 3.26 0.75 1.63 0.75 1.30 1.5 1075 2.8 580 1.5 1075 2.8 640
1/3 5.4 1075 7.7 890 1.00 4.81 1.00 4.35 1.00 2.17 1.00 1.74 --- --- --- --- 2.5 1075 3.7 840
1/2 7.5 1075 9.8 1180 1.50 7.2 1.50 6.52 1.50 3.26 1.50 2.61 --- --- --- --- 3.5 1075 4.7 1070
3/4 8.8 1125 11.1 1330 1.50 7.2 1.50 6.52 1.50 3.26 1.50 2.61 --- --- --- --- 4.4 1125 5.5 1280
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor
manufacturer and Modine. All motors are totally enclosed and all single phase motors have built-in thermal overload protection.
Ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level.
(In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector
hoods.
HP
HP
Table 14.3 - Performance Data - 30°, 60°, and 90° Downward Deflector Hoods
Data Based on unit fired at full rated input, 60° - 80°F entering air temperature, and a 40°F
temperature rise through unit. Maximum mounting heights higher versus units without outlet
devises.
30°
60°
90°
Hood
Type
Max. MTG. HGT.
X
Y
Z
Max. MTG. HGT.
X
Y
Z
Max. MTG. HGT.
S
MOUNTING
HEIGHT
X
Y
Y
Z
Z
X
60 NOZZLE
30 NOZZLE
60
30
30 DOWNTURN NOZZLE
60 DOWNTURN NOZZLE
NOTE:
X = FEED FROM HEATER
TO START OF
FLOOR COVERAGE.
Y = FEET TO END OF
FLOOR COVERAGE.
Z = FEET TO END OF
THROW.
30° HOOD 60° HOOD
30° and 60° THROW-FLOOR COVERAGE
90° HOOD
H
S
S