Brochure

7
6-189.9
GENERAL PERFORMANCE DATA - MODELS HD & PDP
Table 7.1 - Propeller Unit Model HD and PDP General Performance Data
Ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (In Canada see rating plate.)
Reduction of ratings requires use of a high altitude kit.
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor manufacturer and Modine.
Motors on model sizes 100 and above are totally enclosed (model size 75 and below are open drip proof) and all single phase motors have built in thermal overload protection.
Supply
Voltage
Power Code
Model HD Sizes Model PDP Sizes
30 45 60 75 100 125 150 175 200 250 300 350 400
115V
1 Phase
01 (115V)
Motor Amps 2.40 2.40 1.95 1.95 2.50 2.20 2.30 2.80 2.80 5.40 7.50 8.80 8.80
Total Amps 3.70 3.70 3.75 3.75 5.05 4.75 4.05 4.55 5.15 7.75 9.85 11.15 11.15
Transformer kVA n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
208V
1 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 1.00 1.00 0.50 1.00 1.00 1.00 1.50 1.50 1.50
208V Total Amps 2.05 2.05 2.07 2.07 2.79 2.63 2.24 2.52 2.85 4.28 5.45 6.16 6.16
03 (208V)
Motor Amps
n/a n/a n/a n/a n/a n/a n/a
1.00 1.00
n/a n/a n/a n/a
Total Amps 1.90 2.15
230V
1 Phase
01 (115V) with
Transformer
Transformer kVA 0.5 0.5 0.5 0.5 0.75 0.75 0.50 0.75 0.75 1.00 1.50 1.50 1.50
230V Total Amps 1.85 1.85 1.88 1.88 2.53 2.38 2.03 2.28 2.58 3.88 4.93 5.58 5.58
02 (230V)
Motor Amps
n/a n/a n/a n/a n/a n/a
0.80 1.00 1.00 2.20 2.30 4.40 4.40
Total Amps 1.64 1.84 2.28 3.48 3.58 5.68 5.68
208V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 1.00 1.00 0.50 1.00 1.00 1.00 1.50 1.50 1.50
208V Total Amps 2.05 2.05 2.07 2.07 2.79 2.63 2.24 2.52 2.85 4.28 5.45 6.16 6.16
230V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 0.75 0.75 0.50 0.75 0.75 1.00 1.50 1.50 1.50
230V Total Amps 1.85 1.85 1.88 1.88 2.53 2.38 2.03 2.28 2.58 3.88 4.93 5.58 5.58
460V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 0.75 0.75 0.50 0.75 0.75 1.00 1.50 1.50 1.50
460V Total Amps 0.93 0.93 0.94 0.94 1.26 1.19 1.01 1.14 1.29 1.94 2.46 2.79 2.79
575V
3 Phase
01 (115V) with
Transformer
Transformer kVA 0.50 0.50 0.50 0.50 0.75 0.75 0.50 0.75 0.75 1.00 1.50 1.50 1.50
575V Total Amps 0.74 0.74 0.75 0.75 1.01 0.95 0.81 0.91 1.03 1.55 1.97 2.23 2.23
Table 7.2 - Propeller Unit Model HD and PDP Operating Electrical Data
Model HD Sizes Model PDP Sizes
30 45 60 75 100 125 150 175 200 250 300 350 400
Btu/Hr Input
30,000 45,000 60,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr Ouput
24,000 36,000 48,000 60,000 80,000 100,000 120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow
(CFM) @ 70°F
505 720 990 1160 1490 1980 2180 2550 2870 3700 4460 4870 5440
Outlet Velocity (FPM) 523 725 653 769 565 747 931 959 819 1053 1123 1068 1016
Air Temp. Rise (°F) 44 46 45 48 50 47 51 51 52 50 50 53 54
Max. Mounting
Height (Ft.)
10 10 12 14 12 16 16 17 15 19 21 20 19
Heat Throw (Ft.) @
Max Mtg Ht
25 27 36 38 42 56 55 59 51 67 74 70 69
Motor Type
SP SP PSC PSC SP PSC PSC PSC PSC PSC PSC PSC PSC
Motor HP 1/15 1/15 1/12 1/12 1/12 1/8 1/8 1/6 1/6 1/3 1/2 3/4 3/4
Motor RPM 1550 1550 1625 1625 1050 1625 1625 1075 1075 1075 1075 1125 1125
342844 6-189.9.indd 7 11/11/14 9:59 PM