Use and Care Manual

17
6-580.15
START-UP PROCEDURE
Control Operating Sequence
All units are supplied with intermittent pilot systems with
continuous retry control as standard. For intermittent pilot
systems, both the main burner and pilot are turned off 100%
when the thermostat is satisfied. For all units, the system
will attempt to light the pilot for 70 seconds. If the pilot is not
sensed, the ignition control will wait approximately 6 minutes
with the combination gas control closed and no spark. After
6 minutes, the cycle will begin again. After 3 cycles, some
ignition controllers lockout for approximately 1 hour before the
cycle begins again. This will continue indefinitely until the pilot
flame is sensed or power is interrupted to the system. Refer to
Table 18.1 for control code descriptions. Specific descriptions of
the control sequence for different control codes are listed below.
1. The thermostat calls for heat.
2. The power exhauster relay is energized, starting the power
exhauster motor. Once the motor has reached full speed, the
differential pressure switch closes.
3. The pilot valve opens and the ignitor sparks for 70 seconds
in an attempt to light the pilot.
4. Once the pilot is lit, the flame sensor proves the pilot and
stops the ignitor from sparking.
5. On single stage units, the main gas valve is opened and the
main burner is lit to 100% full fire. On two stage units, the
gas valve may open at either 50% or 100%, depending on
what the two stage thermostat is calling for.
6. The air mover starts after 30 to 90 seconds to allow the heat
exchanger to warm up.
7. The unit continues to operate until the thermostat is satisfied,
at which time both the main and pilot valves close 100%.
8. The air mover stops after 30 to 90 seconds to remove
residual heat from the heat exchanger.