Use and Care Manual

12
6-580.14
INSTALLATION - HIGH ALTITUDE ACCESSORY KIT
If the heating value of the gas being supplied is different than
the values shown in Tables 11.1 and 11.2, use the following
equation to determine the appropriate manifold pressure for the
altitude and gas heating value being supplied.
Equation 12.1 - Manifold Pressure for Derated Gas
WHERE:
MP
ACT
= Manifold Pressure (in. W.C.) at Altitude
Manifold pressure setting for the heater being
installed
BTU
TBL
= BTU/ft
3
Content of Gas
Obtained from Tables 11.1 or 11.2 (whichever is
applicable)
BTU
ACT
= BTU/ft
3
Content of Gas
Obtained from the local utility company
MP
SL
= Manifold Pressure (in. W.C.), at Sea Level
Use 3.5" W.C. for natural gas and 10.0" W.C. for
propane gas
NOTE: Only the primary manifold pressure should be adjusted
on units equipped with 2-stage or modulating gas controls. No
adjustments to the low fire manifold pressure are necessary on
these units.