Product Brochure

Request Catalog XXX For Complete Technical Information and Specifications.
6
6-107.17
DO NOT LOCATE ANY GAS-FIRED UNIT IN AREAS WITH CHLORINATED,
HALOGENATED, OR ACIDIC VAPORS IN ATMOSPHERE.
Request Catalog 6-189 (HDB, BDP, BTP), 6-175 (BTS) and 6-170 (BTC)
For Complete Technical Information and Specifications.
GAS-FIRED, BLOWER MODELS
MODEL HDB
MODEL BDP
Blower unit heaters are designed for both heating and ventilating. All Modine gas-fired unit
heater types can be equipped with blowers, including our Hot Dawg
®
low-profile residential
garage heaters and the Effinity
93
®
. In fact, the Effinity
93
®
is the only high efficiency gas-fired
unit heater in North America with this option available.
These units can be used in a variety of ways:
Ducting air in from adjacent spaces for ventilation.
Protecting units from corrosive spaces by mounting them remotely and ducting in warm air.
Where quietness is important, blower fans are lower-noise and can be ducted, unlike
propeller units.
Deflector hoods can be used in areas with higher mounting heights.
Table 6.1 - Power-Exhausted Blower Unit Model HDB and BDP General Performance Data
Model HDB Sizes Model BDP Sizes Model BTP Sizes
60 75 100 125 150 175 200 250 300 350 400 150 175 200 250 300 350 400
Btu/Hr Input j
60,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000 150,000 175,000 200,000 250,000 300,000 350,000 400,l000
Btu/Hr Ouput j
49,200 61,500 82,000 102,500 123,000 143,500 164,000 205,000 246,000 287,000 328,000 123,000 143,500 164,000 205,000 246,000 287,000 328,000
Entering Airflow Range (CFM) 635-1111
794-
1389
1140-
2116
1235-
2058
1587-
2778
1852-
3241
2116-
3704
2646-
4630
3175-
5556
3704-
6481
4233-
6584
1587-
2778
1852-
3241
2116-
3704
2646-
4630
3175-
5556
3704-
6481
4233-
7407
Outlet Velocity
(FPM)
437-726 546-908
443-
781
488-
773
869 892 773 966 1026 1037 1008
Air Temp. Rise (°F) 40-70 40-70 35-65 45-75 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70 40-70
Max. Mounting
Height (Ft.) k
7-13 7-16 8-19 8-17 14 15 13 16 18 19 19 14 8-18 9-21 10-22 11-26 11-26 13-29
Heat Throw (Ft.) @ Max Mtg Ht k
20-45 24-57 27-68 27-59 49 52 47 58 64 67 68 33-75 28-65 32-78 34-78 40-94 39-90 44-102
Table 6.3 - Separated Combusion, High-Efficiency Condensing
Blower Unit Heater Model BTC General Performance Data
Model BTC Sizes
215 260 310
Btu/Hr Input j
215,000 260,000 310,000
Btu/Hr Output j
199,950 241,800 288,300
Condensate Production (Gal./Hr.) 1.6 1.9 2.3
Entering Airflow Range (CFM) 2645-4628 3198-5597 3813-6674
Air Temp. Rise (°F) 40-70 40-70 40-70
Max. Mounting Height (Ft.) l
9-22 11-26 11-26
Heat Throw (Ft.) @ Max. Mtg Ht 33-77 40-94 39-91
Model HDC Sizes Model BTS Sizes
60 75 100 125 150 175 200 250 300 350 400
Btu/Hr Input j
60,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr Ouput j
49,200 61,500 82,000 102,500 123,000 143,500 164,000 205,000 246,000 287,000 328,000
Entering Airflow
Range (CFM)
635-
1111
794-
1389
1140-
2116
1235-
2058
1587-
2778
1852-
3241
2116-
3704
2646-
4630
3175-
5556
3704-
6481
4233-
7407
Air Temp. Rise (°F) 40-70 40-70 35-65 45-75 40-70 40-70 40-70 40-70 40-70 40-70 40-70
Max. Mounting
Height (Ft.) k
7-13 7-16 8-19 8-17 9-21 8-18 9-21 10-22 11-26 11-26 13-29
Heat Throw (Ft.) @
Max Mtg Ht k
20-45 24-57 27-68 27-59 33-75 28-65 32-74 34-78 40-94 39-90 44-102
j Ratings shown are for elevations up to 2,000 Ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet
above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.
k Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and
without deflector hoods.
l Data taken at 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.
Table 6.2 - Separated Combustion Blower Unit Model HDC and BTS General Performance Data
MODEL BTS
MODEL BTC
MODEL BTP