User Guide
Infrared Heater Selection Procedure – Additional Selection Considerations 
9-200.6     9 
Figure 9.1 – Layout for Example 2 
Additional Considerations (All Applications) 
The selection process described for Spot, Partial Area, and 
Total Building Heating applications, while seemingly simple, 
does not consider all variables in the design and layout of the 
infrared heating solution. The following provides additional 
background information on factors to be considered when 
designing the solution. Guidelines and limitations stated in the 
Installation and Service Manuals must also be followed. 
Mounting Height/Building Obstructions 
  For lower mounting heights, use a larger number of 
closely spaced units with lower input ratings. 
  For high mounting heights, use a smaller number of units 
with higher input ratings spaced further apart. 
  Building obstructions such as overhead cranes, lighting, 
and utilities must be avoided. 
Low-Intensity Tube Length Considerations 
  Units with higher input ratings are certified for longer tube 
lengths while units with lower input ratings are certified for 
shorter tube lengths. Please see the Performance Data 
for additional information. 
  A layout as uniform as possible should be used, however 
some areas may be exceptions, such as placing higher 
ratings or a higher number of units with short tube lengths 
where heat loss is greater. Examples include a Northern 
facing wall with a prevailing wind or a frequently opened 
overhead door. 
Clearances to Combustibles and Heat-Affected Objects 
  Clearances to combustible materials must be maintained, 
including areas with stored or stacked materials. See 
pages 4 and 5 for additional information. 
  Clearance to heat affected objects such as sprinkler 
heads must be considered.  Generally, high intensity 
units or the burner and first tube section of the low-
intensity units should be kept at least 6-8 feet from the 
sprinkler head, assuming the sprinkler head is not in the 
direct path of infrared radiant energy. 
Availability of Utilities (Gas and Electric) 
  Availability of gas and electric should be considered. If 
electric service is difficult or costly to extend, high-
intensity units with millivolt controls are an excellent 
choice as external electrical power is not required. 
  As shown in the figure for Example 2, multiple units can 
be positioned end-to-end for common venting, and to 
reduce the amount of gas piping and electricity wiring 
required. This is often a trade-off with optimizing the 
coverage area, which is usually end-to-front positioning. 
Venting/Ventilation 
  High-intensity units require a minimum positive air 
displacement of 4 CFM per 1000 Btu/hr input for natural 
gas or 5 CFM per 1000 Btu/hr input for propane gas. 
Please see the Installation and Service Manuals for 
additional information and requirements. 
  For unvented units, it is important that the building have 
adequate insulation, especially the ceiling. The products 
of combustion, which contain a great deal of moisture, will 
rise in the building. When these moist gases come in 
contact with the cold building surfaces, considerable 
condensation can occur. This moisture can cause a 
great deal of damage and possibly cause safety hazards, 
such as water leaking onto the floor causing slippery 
conditions. 
  For low-intensity units, limitations on the length of flue 
pipe allowed for different ratings and tube system lengths 
exist. These limitations can be found in the Installation 
and Service Manuals. 
  Low intensity units can be common vented in pairs out a 
single larger vent to reduce the number of building 
penetrations for venting and therefore installed cost. 
Units must be of identical burner input rating and tube 
system length and must be controlled by a single 
thermostat. Please refer to the heater Installation and 
Service Manual and the National Fuel Gas Code 
Handbook for additional information and requirements. 
Figure 9.2 – Typical Common Venting 










