User Guide

Performance Data – Total Building Heating
© Modine Manufacturing Company 2016 9-200.6
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, Wisconsin 53403-2552
Telephone: 1.800.828.4328 (HEAT)
Fax: 1.800.204.6011
www.modine.com
The data on this page applies only to Total Building Heating applications as discussed on page 8.
Table 12.1 – Suggested Heater Placement for Low Intensity Infrared Heaters (ft)
Input Rating (Btu/hr) 50,000 60,000 75,000 100,000 125,000 150,000 175,000 200,000
Mounting Height 10-12 10-12 12-14 12-14 15-22 15-25 18-28 20-30
Between Burners 10-15 10-15 10-25 15-35 15-38 15-45 20-50 25-60
Unit to Wall (min) 3-15 3-15 3-15 3-25 3-28 3-30 4-35 4-40
Between Rows 40-50 40- 50 50-60 60-70 60-70 60-80 60-80 60-80
Minimum Clearance
to Combustibles
See Pages 4 and 5
A
vailable Certified Tube Lengths (feet)
IPT Models
20,30 20,30,40 20,30,40
30,40,50
40,50,60 50,60 50,60,70 50,60,70
The heater placement chart is suggested under normal circumstances. Building
design and obstructions and application differences may require adjustments.
See the figure at the right for graphical depiction of distances indicated.
Minimum clearance to combustibles must be maintained at all times.
Propane operation not available on the following models:
IPT75 with 40 foot tube system length
IPT100 with 50 foot tube system length
Table 12.2
Suggested Heater Placement for High Intensity Infrared Heaters
IHR Model Size (MBH): 30 60 90 130 160
Mounting Height by Mounting Angle (ft)
30° (max) 14-15 14-16 16-18 21-24 24-28
Between Units 8-20 15-30 21-42 28-50 30-55
Unit to Wall (min) 4 6 6 8 8
Between Rows (max) 40 55 70 85 100
Minimum Clearance to
Combustibles
See Pages 4 and 5
The heater placement chart is suggested under normal circumstances.
Building design and obstructions and application differences may require adjustments.
See the figure at the right for graphical depiction of distances indicated.
Minimum clearance to combustibles must be maintained at all times.
Between Burners
Unit to Wall
Between Rows
Between Units
Unit to Wall
Between Rows