Install Instructions
THIS MANUAL IS THE PROPERTY OF THE OWNER. 
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB. 
1-550.26
5H70718A
February, 2011
INSTALLATION AND SERVICE MANUAL
steam/hot water unit heaters
Inspection On Arrival
1.  Inspect unit upon arrival. In case of damage, report it 
immediately to transportation company and your local factory 
sales representative.
2.  Check rating plate on unit to verify that power supply meets 
available electric power at point of installation.
3.  Inspect unit received for conformance with description of 
product ordered (including specifications where applicable).
General Information
Installation and service instructions in this manual are applicable 
to the three types of steam/hot water unit heaters which should 
be installed in their proper applications for their most effective 
function as overhead heating units.
The copper coils are warranted for operation at steam or 
hot water pressures up to 150 lbs. per sq. in. gauge, and 
or temperatures up to 375°F, cupronickel tube units are 
warranted for operating pressures up to 250 PSI and operating 
temperatures up to 400°F. Canadian Standards Association 
(CSA) requriements state that explosion-proof units may not 
be used with a fluid temperature in excess of 329°F and still 
maintain their explosion-proof rating, for national electric code 
ignition temperature rating T3B for grain dust.
Motors are designed for continuous duty. They can operate in a 
maximum ambient temperature of 104°F (40°C).
The unit heaters are listed by the Canadian Standards 
Association as certified and Canadian Registered heat 
exchangers CRN OH 9234.5.
Steam horizontal and vertical delivery unit heaters are available 
in both standard and low-outlet temperature models. Low outlet 
temperature models are recommended primarily for installation 
on heating systems with steam pressures of 30 to 150 PSI. 
When used at these steam pressures they provide lower outlet 
air temperatures for longer heat throw and, because of wider 
fin spacing, they are less susceptible to clogging in dusty 
atmospheres.
The model number of each unit heater indicates its rated Btu/Hr. 
capacity/1000 at 2 lbs. steam pressure and 60°F entering air 
temperature. For example an HSB-63 has an output of 63,000 
Btu/Hr. at 2 lbs. steam and 60°F entering air.
C
US
®
Model HSB
Horizontal Delivery
Top/Bottom
Inlet/Outlet
Model HC
Horizontal Delivery
Side 
Inlet/Outlet
Models V/VN
Vertical Delivery
Model PT/PTN
“Power-throw”
IMPORTANT
The use of this manual is specifically intended 
for a qualified installation and service agency. 
A qualified installation and service agency must 
perform all installation and service of these 
appliances.
CAuTION
Do not remove outlet fan guard from vertical 
type unit heaters.