Specification

page 2 of 2
Commercial HVAC&R Division Modine Manufacturing Company 1500 DeKoven Avenue Racine, Wisconsin 53403-2552
Phone: 1.800.828.4328 (HEAT) Fax: 262.636.1665 www.modine.com
© Modine Manufacturing Company 2005 8/05 - Litho in USA
Table 2.1
Motor Data
1-451.13 SUBMITTAL DATA
Ratings shown are for Standard and Low Outlet Temperature Models.
Motor HP listed for power code 01.
For supply voltages of 200V/60Hz/1ph and all non-explosion proof 3 phase voltages of 200, 230, 460 and 575, Model Numbers indicated with Note , require
that a 115V/60Hz/1 phase Power Code 01 unit heater be used with a shipped loose accessory transformer. See Table 2.2 for Transformer Sizes.
Motor Type, Voltage and Power Code
115/60/1 200/60/1 230/60/1 200-208/60/3 230/460/3 575/60/3 115/60/1 230/460/60/3
01 N/A 02 04 05 10 06 09
Model Number Motor HP Amps Amps Amps Amps Amps Amps Amps Amps
HSB/HC-18 1/60 0.8 0.44 3.1 -
HSB/HC-24 1/25 1.6 0.44 3.1 -
HSB/HC-33 1/25 1.6 1 3.1 -
HSB/HC-47 1/12 2.2 1 3.1 -
HSB/HC-63 1/12 2.2 1 3.1 -
HSB/HC-86 1/8 2.3 1 3.1 -
HSB/HC-108 1/8 2.3 1 3.1 -
HSB/HC-121 1/5 2.8 1.5 4.1 1.5/0.75
HSB/HC-165 1/3 5.4 2.23 6.1 1.5/0.75
HSB/HC-193 1/3 5.4 2.23 6.1 1.5/0.75
HSB/HC-258 1/2 7.5 3.5 5.8 2.0/1.0
HSB/HC-290 1/2 7.5 3.5 5.8 2.0/1.0
HSB/HC-340 1/2 7.5 3.5 5.8 2.0/1.0
Totally Enclosed w/Thermal Overload
Explosion Proof
w/Thermal Overload
Figure 2.1
Field Installed Transformer Accessory
Table 2.2 - Step-Down Transformer Accessory Selection
200V/60Hz/1 230/460V/ 575V/60Hz/
or 3 phase 60Hz/3 phase 3 phase
Model Number kVA kVA kVA
HSB 18-63 0.25 0.25
HSB 86-121 0.50 0.50
HSB165-193 1.00 0.75 0.75
HSB258-340 1.00 1.00
kVA Size Ship Wt. (Lb.)
0.25 7
0.50 13
0.75 15
1.00 19
0.50
1.00