Figure 2.1 - Model HHD Standard Features
Electrical Conduit Entry
(not pictured - see page 4)
Mounting Brackets with
Vibration Isolators
Hot Water Supply/Return
Piping Connections
Electrical J-Box Access Door
(not pictured - see page 4)
Unit Serial PlateSolid State Motor Speed Control
Note: Standard piping/electrical access side orientation shown.
Feature
General
All units are listed by ETL as design certied for use in
both the US and Canada to the UL 1995 - latest revision
and CSA C22.2 No. 236 Standards for Heating and
Cooling Equipment for safe operation, construction,
and performance.
Low prole design is ideally suited for residential
garages, basements, vestibules, commercial, industrial,
institutional installations.
Non-potable water applications only.
Cabinet
Low prole, 18 gauge steel cabinet results in a clean
appearance that maximizes head room.
Cabinet pre-treated for prevention of rust and corrosion
and nished with a durable electrostatically applied
baked-on polyester powdercoat paint.
Environmentally friendly.
Attractive Hammertone Beige paint color.
Horizontal adjustable air-deector blades.
Fingerproof inlet air openings.
Side access piping and electrical (see “Mounting
Flexibility” for info on reversing access side).
Two L-shaped mounting brackets (see “Mounting
Flexibility” for mounting orientations).
Mounting Flexibility
Brackets designed to match up to standard 16”
on-center joist spacing.
Mounting orientation exibility includes (refer to
Figure 2.2):
• Horizontal air delivery, mounted parallel to joists.
Horizontal air delivery, mounted perpendicular to
joists.
• Vertical air delivery, mounted between joists.
Electrical connections are standard on the left with
piping on the right. Access sides can be easily reversed
in the eld by simply ipping the unit over.
Heating Coil
High capacity, 2-row hot water coil.
Copper tubes mechanically expanded into aluminum ns
for maximum heat transfer.
1/2" NPT piping connections.
Coils suitable for water pressures up to 150PSI and
temperature up to 200°F.
Air
Mover
Twin centrifugal blower wheels for quieter operation.
Dual shaft blower motor (115V/60Hz/1ph).
Factory supplied neoprene vibration isolators.
Table 2.1 - Standard Features Figure 2.2 - Model HHD Mounting Orientations
Horizontal Air Delivery,
Perpendicular to Joists
Horizontal Air Delivery,
Parallel to Joists
Vertical Air Delivery,
Recessed Between Joists