Instructions / Assembly

PERFORMANCE DATA
12 1-500.3
Table 9.1 – Performance Data 
Entering Water Temperature (60°F Entering Air Temperature)
Model
Size
Airflow
CFM GPM
WPD 120°F 140°F 160°F 180°F 200°F
(ft. Water) Btu/Hr WTD Btu/Hr WTD Btu/Hr WTD Btu/Hr WTD Btu/Hr WTD
30
405
(High
Speed)
1
0.6 11,900 25 15,800 33 19,800 41 23,700 49 27,700 58
2
2.2 15,500 16 20,600 22 25,800 27 30,900 32 36,100 38
3
4.7 17,200 12 22,900 16 28,600 20 34,400 24 40,100 28
4
7.9 18,200 10 24,200 13 30,300 16 36,300 19 42,400 22
5
12.0 19,600 8 26,100 11 32,600 14 39,200 16 45,700 19
280
(Low
Speed)
1
0.6 9,100 19 12,200 25 15,200 32 18,300 38 21,300 44
2
2.2 12,000 13 15,900 17 19,800 21 23,800 25 27,800 29
3
4.7 13,200 9 17,600 12 22,000 15 26,400 18 30,800 21
4
7.9 14,000 7 18,600 10 23,300 12 27,900 15 32,600 17
5
12.0 15,100 6 20,100 8 25,100 10 30,200 13 35,200 15
45
710
(High
Speed)
1
0.6 17,200 36 22,900 48 28,600 60 34,400 72 40,100 84
2
2.2 22,400 23 29,900 31 37,300 39 44,800 47 52,300 55
3
4.7 24,900 17 33,200 23 41,500 29 49,800 35 58,100 40
4
7.9 26,400 14 35,100 18 43,900 23 52,700 27 61,500 32
5
12.0 28,400 12 37,800 16 47,300 20 56,800 24 66,300 28
425
(Low
Speed)
1
0.6 11,900 25 15,900 33 19,900 41 23,900 50 27,900 58
2
2.2 15,600 16 20,700 22 25,900 27 31,100 33 36,300 38
3
4.7 17,300 12 23,000 16 28,800 20 34,600 24 40,300 28
4
7.9 18,300 10 24,400 13 30,500 16 36,600 19 42,700 22
5
12.0 19,700 8 26,300 11 32,800 14 39,400 16 46,000 19
For conditions other than shown above, please refer to the Modine Breeze AccuSpec program for detailed performance data.
Allowable water temperature range is 100°F to 200°F. Allowable indoor air temperature range is 40°F to 100°F. If temperatures below freezing
are expected, provisions should be made to either drain the unit heater coil or utilize a continually circulating glycol solution.
Useful Formulas:
Air Temperature Rise
The air temperature rise can be calculated by the following formula:
Air Temp Rise =
Btu/Hr
1.08 x CFM
Example:
What is the Air Temp Rise for a model size 45 unit, operating at high speed, 140°F entering water, 3 GPM flow rate?
From Table 9.1, the output is 33,200 Btu/Hr. The air temperature rise, per the formula above, is:
Air Temp Rise =
33,200 Btu/Hr
= 43°F
1.08 x 710CFM
Final Air Temperature
The final discharge air temperature can be calculated by the following formula:
Final Air Temperature = Air Temperature Rise + Entering Air Temperature
Example:
What is the Final Air Temperature for the previous example?
The air temperature rise was previously calculated to be 43°F. The final air temperature, per the formula above, is:
Final Air Temperature = 43°F + 60°F = 103°F