PERFORMANCE DATA
12 1-500.3
Table 9.1 – Performance Data •‚
Entering Water Temperature (60°F Entering Air Temperature)
Model
Size
Airflow
CFM GPM
WPD 120°F 140°F 160°F 180°F 200°F
(ft. Water)
Btu/Hr WTD
Btu/Hr WTD
Btu/Hr WTD
Btu/Hr WTD
Btu/Hr WTD
30
405
(High
Speed)
1
0.6 11,900 25 15,800 33 19,800 41 23,700 49 27,700 58
2
2.2 15,500 16 20,600 22 25,800 27 30,900 32 36,100 38
3
4.7 17,200 12 22,900 16 28,600 20 34,400 24 40,100 28
4
7.9 18,200 10 24,200 13 30,300 16 36,300 19 42,400 22
5
12.0 19,600 8 26,100 11 32,600 14 39,200 16 45,700 19
280
(Low
Speed)
1
0.6 9,100 19 12,200 25 15,200 32 18,300 38 21,300 44
2
2.2 12,000 13 15,900 17 19,800 21 23,800 25 27,800 29
3
4.7 13,200 9 17,600 12 22,000 15 26,400 18 30,800 21
4
7.9 14,000 7 18,600 10 23,300 12 27,900 15 32,600 17
5
12.0 15,100 6 20,100 8 25,100 10 30,200 13 35,200 15
45
710
(High
Speed)
1
0.6 17,200 36 22,900 48 28,600 60 34,400 72 40,100 84
2
2.2 22,400 23 29,900 31 37,300 39 44,800 47 52,300 55
3
4.7 24,900 17 33,200 23 41,500 29 49,800 35 58,100 40
4
7.9 26,400 14 35,100 18 43,900 23 52,700 27 61,500 32
5
12.0 28,400 12 37,800 16 47,300 20 56,800 24 66,300 28
425
(Low
Speed)
1
0.6 11,900 25 15,900 33 19,900 41 23,900 50 27,900 58
2
2.2 15,600 16 20,700 22 25,900 27 31,100 33 36,300 38
3
4.7 17,300 12 23,000 16 28,800 20 34,600 24 40,300 28
4
7.9 18,300 10 24,400 13 30,500 16 36,600 19 42,700 22
5
12.0 19,700 8 26,300 11 32,800 14 39,400 16 46,000 19
• For conditions other than shown above, please refer to the Modine Breeze AccuSpec program for detailed performance data.
‚ Allowable water temperature range is 100°F to 200°F. Allowable indoor air temperature range is 40°F to 100°F. If temperatures below freezing
are expected, provisions should be made to either drain the unit heater coil or utilize a continually circulating glycol solution.
Useful Formulas:
Air Temperature Rise
The air temperature rise can be calculated by the following formula:
Air Temp Rise =
Btu/Hr
1.08 x CFM
Example:
What is the Air Temp Rise for a model size 45 unit, operating at high speed, 140°F entering water, 3 GPM flow rate?
From Table 9.1, the output is 33,200 Btu/Hr. The air temperature rise, per the formula above, is:
Air Temp Rise =
33,200 Btu/Hr
= 43°F
1.08 x 710CFM
Final Air Temperature
The final discharge air temperature can be calculated by the following formula:
Final Air Temperature = Air Temperature Rise + Entering Air Temperature
Example:
What is the Final Air Temperature for the previous example?
The air temperature rise was previously calculated to be 43°F. The final air temperature, per the formula above, is:
Final Air Temperature = 43°F + 60°F = 103°F