Wiring Guide
WIRING DIAGRAMS – THERMOSTAT & SUMMER/WINTER SWITCH 
13     6-461.1 
Single Stage Thermostat & Summer/Winter Switch Wiring 
Y
G
R
C
W
W
G
1-STAGE LOW VOLTAGE ROOM
STAT WITH SUB-BASE SWITCHING
(BY OTHERS)
R C
W
1-STAGE LOW VOLTAGE ROOM
STAT WITH NO SWITCHING
(BY OTHERS)
R C
TERMINAL STRIP
ON UNIT HEATER
SUMMER/WINTER
SWITCH
(BY OTHERS)
WINTER
SUMMER
FAN OPERATION:
SUMMER - CONTINUOUS FAN
WINTER - INTERMITTENT FAN ON A CALL FOR HEAT
FAN OPERATION (BASED ON FAN SUB-BASE SWITCH):
SWITCH = ON - CONTINUOUS
SWITCH = AUTO - INTERMITTENT ON A CALL FOR HEAT
TERMINAL STRIP
ON UNIT HEATER
1-STAGE ROOM STAT
W
ITH SUB-BASE FAN SWITCH
SUMMER/WINTER SWITCH & 1-STAGE ROOM STAT
W
ITHOUT SUB-BASE FAN SWITCH
Y
G
R
C
W
W
G
1-STAGE LOW VOLTAGE ROOM
STAT WITH SUB-BASE SWITCHING
(BY OTHERS)
R C
FAN OPERATION (BASED ON FAN SUB-BASE SWITCH):
SWITCH = ON - CONTINUOUS
SWITCH = AUTO - INTERMITTENT ON A CALL FOR HEAT
TERMINAL BOARD
ON UNIT HEATER
T2
FG
CVT1
MODELS HD/HDB, HDS/HDC, AND PTS/BTS MODEL PTC
W
1-STAGE LOW VOLTAGE ROOM
STAT WITH NO SWITCHING
(BY OTHERS)
R C
TERMINAL BOARD
ON UNIT HEATER
SUMMER/WINTER
SWITCH
(BY OTHERS)
FAN OPERATION:
SUMMER - CONTINUOUS FAN
WINTER - INTERMITTENT FAN ON A CALL FOR HEAT
T2
FG
CVT1
WINTER
SUMMER
Two Stage Thermostat & Summer/Winter Switch Wiring 
G
W1
C
R
W2
W2
G
W1
2-STAGE LOW VOLTAGE ROOM
STAT WITH SUB-BASE SWITCHING
(BY OTHERS)
R C
G
W1
C
R
W2
W2
W1
NOTE:
GENERIC ROOM STAT TERMINALS SHOWN. ACTUAL STAT MAY USE DIFFERENT TERMINALS AND/OR
WIRING. PLEASE CONSULT WIRING INSTRUCTIONS FOR STAT FOR PROPER WIRING.
2-STAGE LOW VOLTAGE ROOM
STAT WITH NO SWITCHING
(BY OTHERS)
R
C
TERMINAL STRIP
ON UNIT HEATER
SUMMER/WINTER
SWITCH
(BY OTHERS)
FAN OPERATION:
SUMMER - CONTINUOUS FAN
WINTER - INTERMITTENT FAN ON A CALL FOR HEAT
FAN OPERATION (BASED ON FAN SUB-BASE SWITCH):
SWITCH = ON - CONTINUOUS
SWITCH = AUTO - INTERMITTENT ON A CALL FOR HEAT
TERMINAL STRIP
ON UNIT HEATER
2-STAGE ROOM STAT
W
ITH SUB-BASE FAN SWITCH
SUMMER/WINTER SWITCH & 2-STAGE ROOM STAT
W
ITHOUT SUB-BASE FAN SWITCH
MODELS HD/HDB, HDS/HDC, AND PTS/BTS
WINTER
SUMMER
Notes on Thermostat and Summer/Winter Switch 
Wiring: 
Units are equipped as standard with a controller that 
activates the unit fan in either of the following ways: 
•  On a call for heat (thermostat closure between R & W 
terminals (W1 for 2-stage units) on the unit heater 
terminal strip (T1 & T2 on the external terminal board 
for model PTC units). The control automatically 
recognizes a call for heat as requiring fan operation. 
•  With switch closure between R & G terminals on the 
unit heater terminal strip (T1 & G on the external 
terminal board for model PTC units). The control 
recognizes this as an override to the fan control based 
on a call for heat and starts the fan. 
The diagrams on this page are arranged as follows: 
1.  Single stage thermostat with a Fan On/Auto switch for 
fan control. 
2.  Single stage thermostat without a Fan On/Auto switch 
and a Summer/Winter switch for fan control. 
3.  Two stage thermostat with a Fan On/Auto switch for 
fan control. 
4.  Two stage thermostat without a Fan On/Auto switch 
and a Summer/Winter switch for fan control. 
Note: A Summer/Winter switch used on these models does 
NOT require a control relay as was required on previous 
models. 