Submittal Sheet
AccuSpec V4.6.1
GENERAL PERFORMANCE DATA
General Performance Data
Model
HD 75
At 0’ Elevation
Btu/Hr. Input
75,000
Btu/Hr. Output
61,500
Entering Airflow (CFM)
1160
Outlet Velocity
769
Air Temp. Rise (°F)
48
Mounting Height (Max Ft.)
1
14
Heat Throw (Max. Mtg. Ft.)
2
38
Unit Total Power (Amps)
3.25
As Configured at 0-2000 Ft. Elevation
Btu/Hr. Input
75,000
Btu/Hr. Output
61,500
Configured Air Temp Rise (°F)
49
Motor Data
Horse Power
1/12
RPM
1625
Type
P.S.C.
Motor Amps at 115V
1.95
Clearances to Combustibles
Top and Bottom
1”
Vent Connector
4”
Access Side
18”
Non-Access Side
1”
Rear
18”
1
At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit.
2
Heat Throws are calculated at 65°F ambient with a 49°F air temperature rise with the unit mounted at a
maximum mounting height of 14 feet.