User Guide
1-558.0
UNIT LOCATION
1. Units should not be installed in atmospheres where 
corrosive fumes or sprays are present.
2. Be sure no obstructions block air intake or air discharge of 
unit heater.
3. Locate horizontal delivery unit heaters so air streams of 
individual units wipe the exposed walls of the building 
with either parallel or angular flow without blowing directly 
against the walls. Heaters should be spaced so the air 
stream from one supports the air stream from another 
heater. See Figure 3.1.
4. Columns, machinery, partitions, and other obstacles should 
not interfere with air streams from unit heaters.
5. Unit heaters installed in a building exposed to a prevailing 
wind should be located to direct a major volume of heated 
air along the windward wall of the building.
6. Horizontal delivery unit heaters with 90° hoods should 
generally be located in the central area of the space to be 
heated. Place horizontal delivery units without hoods along 
the walls of the same building where heat loss is usually 
greatest. See Figure 3.3.
7. Arrange horizontal delivery units so they do not blow directly 
at occupants. Air streams from this type of unit should be 
directed down aisles, into open spaces on the floor, or along 
exterior walls.
8. When only Horizontal delivery units with 90° hoods are 
installed, they should be located so exposed walls are 
blanketed by their air streams. See Figure 3.2.
UNIT MOUNTING 
Do not install unit above recommended maximum mounting 
heights. Height at which unit heaters are installed is critical. 
Maximum mounting heights for all units are listed in Table 4.1 
and the height dimensions are shown in Figures 4.3 and 4.4. 
Maximum mounting heights for horizontal models are given for 
units with or without optional air deflectors. The data in Table 
4.1 is based on operating conditions of 140°F entering water 
with 60°F entering air. When operating conditions are other 
than those above, refer to Figure 4.2 for maximum mounting 
height correction factor. To obtain the maximum mounting at 
actual operating conditions, multiply the appropriate factor from 
Figure 4.2 by the mounting height in Table 4.1. The maximum 
mounting height for all units is that height above which the unit 
heater will not deliver heated air to the floor at standard rating 
conditions.
Deflector Mounting
If an optional air deflector has been furnished, it is always 
shipped separately and can be attached to the unit before 
suspension. Vertical louvers for horizontal units can also be 
added and positioned before installation. Refer to mounting 
instructions which are furnished with each deflector.
Figure 3.2 - Unit Locations of Horiontal Units With 
90° Hoods In Narrow Buildings
Figure 3.1 - Horizontal Delivery Unit Location
Figure 3.3 - Combination Horizontal and Vertical 
Delivery Unit Installation
UNIT LOCATION / UNIT MOUNTING
3
CAUTION
Do not install units below 8 feet measured from the bottom of 
the unit to the floor.
 DANGER
Appliances with power codes 01, 02, 04, 05, and 10 must 
not be installed where they may be exposed to a potentially 
explosive or flammable atmosphere.










