Target Capacity 67,000
Entering Air Temp 60F
Entering Water Temp 140F
Leaving Water Temp 120F
Unit Selection Lodronic™ HCH 67 HC 165
Capacity 67,000 67,000
Leaving Air Temp 114F 79F
Water Flow 6.7 GPM 7 GPM
Pressure Drop 2.6 ft. wc. 2.6 ft. wc.
Dimensions 22.5” x 29” x 25.6” 32” x 32” x 23.5”
Weight 79.5 lbs 92 lbs
Motor Amp Draw 2.5 A 4.6 A
Sound @ 10’ 53.9 dbA 62.2 dbA
Sound @ 15’ 49.7 dbA 58.9 dbA
Connections 1” female sweat on same side 1-1/4” NPT on opposite unit sides
Mounting Height 9’ 20’
Heat Throw 32.9’ 43’
Mounting Height w/ 60 Hood 16’ Not Available
Heat Throw w/ 60 Hood @ max mounting height 22’ Not Available
Mounting Height w/ 90 Hood 24’ Not Available
Follow us @ModineHVAC
See us at YouTube.com/ModineHVAC
www.facebook.com/ModineHVAC/
www.linkedin.com/company/modinehvac/
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, Wisconsin 53403-2552
Standard Features
• High-temperature output vs older traditional systems
• High-efciency 4-row coil with low water pressure drop
• Smaller fan and motor for a lower system amp draw
• Designed for lower entering hot water temperatures
Select from Six Sizes to Perfectly Match Your Application
• 22k to 195k BTU/hr
• 370 to 3200 CFM
• 115, 208, 240, 480, 575V/ I phase
• 208, 240, 480, 575V/ 3 phase
*Hazardous location construction available
LOW-TEMPERATURE HOT WATER UNIT VS STANDARD OVERSIZED UNIT
©2019 Modine Manufacturing Co.