Brochure

1-150.11
23
PERFORMANCE DATA
Motor Data, Step-Down Transformer Accessory Data
Ratings shown are for Standard and Low Outlet Temperature Models.
All HSB/HC units, V/VN-42 thru V/VN,PT/PTN-333 motor HP listed for power code 01. V/VN,PT/PTN333 thru V/VN,PT/PTN610 motor HP listed for power code 04 and
V/PT-952 motor HP listed for power code 05.
For model
sizes V/VN/PT/PTN385 and above, motors for Power Codes 04, 05, and 10 do not have thermal overload protection.
For supply voltages
of 208V/60Hz/1ph and all non-explosion proof 3 phase voltages of 208, 230, 460 and 575, Model Numbers indicated with Note , require that a
115V/60Hz/1 phase Power Code 01 unit heater be used with a shipped loose accessory transformer. See Table 23.2 for Transformer Sizes.
For
non-explosion proof 3 phase supply voltages of 208, 230, and 460, Model Numbers indicated with Note , can be ordered with a Power Code (208V/3ph=04,
230/460V/3ph=05) that provides a motor matched to the supply voltage with amp draw as shown. Alternately, a 115V/60Hz/1 phase Power Code 01 unit heater could
be used with a shipped loose accessory transformer. See Table 23.2 for Transformer Sizes.
Table 23.1 - Motor Data
Motor Type, Voltage and Power Code
115/60/1 208/60/1 230/60/1 208/60/3 230/460/3 575/60/3 115/60/1 230/460/60/3
01 N/A 02 04 05 10 06 09
Model Number Motor HP Amps Amps Amps Amps Amps Amps Amps Amps
HSB/HC-18 1/60 0.8 0.44 3.1 -
HSB/HC-24 1/25 1.6 0.44 3.1 -
HSB/HC-33 1/25 1.6 1 3.1 -
HSB/HC-47 1/12 2.2 1 1.4/0.4 3.1 -
HSB/HC-63 1/12 2.2 1 1.4/0.4 3.1 -
HSB/HC-86 1/8 2.3 1 1.4/0.4 3.1 -
HSB/HC-108 1/8 2.3 1 1.4/0.4 3.1 -
HSB/HC-121 1/5 2.8 1.5 1.9 2.1/1.05 4.1 1.5/0.75
HSB/HC-165 1/3 5.4 2.23 1.9 2.1/1.05 6.1 1.5/0.75
HSB/HC-193 1/3 5.4 2.23 1.9 2.1/1.05 6.1 1.5/0.75
HSB/HC-258 1/2 7.5 3.5 2.6 3.0/1.5 5.8 2.0/1.0
HSB/HC-290 1/2 7.5 3.5 2.6 3.0/1.5 5.8 2.0/1.0
HSB/HC-340 1/2 7.5 3.5 2.6 3.0/1.5 5.8 2.0/1.0
V/VN-42 1/30 1.9 1.28 1.9 2.1/1.05 4.1 -
V/VN-59 1/30 1.9 1.28 1.9 2.1/1.05 4.1 -
V/VN-78 1/15 2.4 1.28 1.9 2.1/1.05 4.1 -
V/VN-95 1/15 2.4 1.28 1.9 2.1/1.05 4.1 -
V/VN-139 1/5 2.8 1.5 1.9 2.1/1.05 4.1 1.5/.75
V/VN-161 1/3 5.4 2.23 1.9 2.1/1.05 6.1 1.5/.75
V/VN-193 1/3 5.4 2.23 1.9 2.1/1.05 6.1 1.5/.75
V/VN-212 1/3 5.4 2.23 1.9 2.1/1.05 6.1 1.5/.75
V/VN-247 1/2 7.5 3.5 2.6 3.0/1.5 5.8 2.0/1.0
V/VN, PT/PTN-279 1/2 7.5 3.5 2.6 3.0/1.5 5.8 2.0/1.0
V/VN, PT/PTN-333 3/4 8.8 4.4 3.7 3.5/1.8 - -
V/VN, PT/PTN-385 1 - - - 4 4.0/2.0 1.5 - 3.5/1.75
V/VN, PT/PTN-500 1-1/2 - - - 5.8 5.2/2.6 2 - 5.8/2.9
V/VN, PT/PTN-610 1-1/2 - - - 5.8 5.2/2.6 2 - 5.8/2.9
V, PT-952 2 - - - - 6.8/3.4 - - 6.2/3.1
Totally Enclosed w/Thermal Overload
Explosion Proof w/
Thermal Overload
Figure 23.1
Field Installed Transformer Accessory
Table 23.2 - Step-Down Transformer Accessory Selection
208V/60Hz/1 230/460V/ 575V/60Hz/
or 3 phase 60Hz/3 phase 3 phase
Model Number kVA kVA kVA
HSB/HC 18-63 0.25 0.25
HSB/HC 86-121 0.50 0.50
HSB/HC165-193 1.00 0.75 0.75
HSB/HC258-340 1.00 1.00
V/VN 42-59 0.50 0.25 0.25
V/VN 78-139 0.50 0.50
V/VN161-212 1.00 0.75 0.75
V/VN247-333 1.00 1.00
PT/PTN279-333 1.00 1.00 1.00
kVA Size Ship Wt. (Lb.)
0.25 7
0.50 13
0.75 15
1.00 19
0.50
1.00
0.50
1.00